M 2001d Digital Tapchanger ControlHardware / appliance · Beckwithelectric

CVE-2014-9201

MEDIUM · 6.4 CVSS v2.0 Published 2015-06-05
Fix available
A fix is available. Upgrade to after 04.07.00 or later.
See remediation →
73/100
Remediation priority · Elevated
Remotely reachable No privileges Zero-click

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
Beckwith Electric M-6200 Digital Voltage Regulator Control with firmware before D-0198V04.07.00, M-6200A Digital Voltage Regulator Control with firmware before D-0228V02.01.07, M-2001D Digital Tapchanger Control with firmware before D-0214V01.10.04, M-6283A Three Phase Digital Capacitor Bank Control with firmware before D-0346V03.00.02, M-6280A Digital Capacitor Bank Control with firmware before D-0254V03.05.05, and M-6280 Digital Capacitor Bank Control do not properly generate TCP initial sequence number (ISN) values, which makes it easier for remote attackers to spoof TCP sessions by predicting an ISN value.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · high confidence

Beckwith Electric digital voltage regulator and capacitor bank control devices use a weak TCP Initial Sequence Number (ISN) generation algorithm that produces predictable sequence numbers. This allows remote attackers to perform TCP session spoofing or hijacking by predicting the next ISN value in the TCP three-way handshake.

MitigationUpdate affected device firmware to the specified minimum versions (D-0198V04.07.00, D-0228V02.01.07, D-0214V01.10.04, D-0346V03.00.02, or D-0254V03.05.05 depending on model). If immediate patching is not feasible, implement network segmentation and add encryption/authentication layers (TLS, IPSec) to protect TCP sessions.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

Affected products & versions What the vendor confirmedThe version ranges the vendor confirmed as vulnerable. If your version sits inside a range here, treat yourself as exposed until you have upgraded.

NVD · CPE data
M 2001d Digital Tapchanger ControlHardware / appliance
Affected:all versions
M 6200 Digital Voltage Regulator ControlHardware / appliance
Affected:all versions
M 6200a Digital Voltage Regulator ControlHardware / appliance
Affected:all versions
M 6280 Digital Capacitor Bank ControlHardware / appliance
Affected:all versions
M 6280a Digital Capacitor Bank ControlHardware / appliance
Affected:all versions
M 6283a Three Phase Digital Capacitor Bank ControlHardware / appliance
Affected:all versions
M 2001d Digital Tapchanger Control D 0214 FirmwareOperating system
Affected:<= 01.10.04
M 6200 Digital Voltage Regulator Control D 0198 FirmwareOperating system
Affected:<= 04.07.00

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
Low
Authentication
None
Confidentiality
Partial
Integrity
None
Availability
Partial

AV:N/AC:L/Au:N/C:P/I:N/A:P

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Identify the device model
    Access the device management interface or check device labeling to confirm the exact model (M 2001d, M 6200, M 6200a, M 6280, M 6280a, or M 6283a)
    Affected if The device is any of these Beckwith Electric models listed as affected
  2. Check the firmware version
    Log into the device web interface or console and navigate to the firmware/version information section. For M 2001d, look for D 0214 firmware version. For M 6200, look for D 0198 firmware version.
    Affected if Firmware version is <= 01.10.04 for M 2001d (D 0214) or <= 04.07.00 for M 6200 (D 0198), or if the device is any other affected model running any firmware version
  3. Confirm TCP services are exposed
    Scan the device network ports using nmap or similar tool to identify open TCP ports (common industrial protocols may use ports 502, 102, or custom ports)
    Affected if The device has accessible TCP ports exposed on the network
  4. Verify network accessibility
    Determine if the affected device TCP ports are reachable from untrusted network segments or the internet
    Affected if The device TCP services are reachable from network segments outside the trusted control network

The environment is affected if any Beckwith Electric M 2001d, M 6200, M 6200a, M 6280, M 6280a, or M 6283a device with vulnerable firmware is exposed on the network, since the weak ISN algorithm affects all versions of these devices.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

From vendor data
Upgrade available Upgrade to a release after 04.07.00
Interim mitigation

Update affected device firmware to the specified minimum versions (D-0198V04.07.00, D-0228V02.01.07, D-0214V01.10.04, D-0346V03.00.02, or D-0254V03.05.05 depending on model). If immediate patching is not feasible, implement network segmentation and add encryption/authentication layers (TLS, IPSec) to protect TCP sessions.

Fix this in M 2001d Digital Tapchanger Control Scoped from the published advisory
  • Consultation8.0 h
  • Implementation16.0 h
  • Testing12.0 h
  • Review / QA4.0 h
40.0 hours of engineering $7,000
Get the upgrade done

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $11,200.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2014-9201 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2014-9201 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data