Simatic S7 300 Cpu FirmwareOperating system · Siemens

CVE-2016-9159

MEDIUM · 5.9 CVSS v3.1 Published 2016-12-17
Mitigation only
No fix yet — a mitigation exists. There is no fixed release. A documented workaround reduces exposure in the meantime.
See remediation →
68/100
Remediation priority · Elevated
Remotely reachable No privileges Zero-click

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
A vulnerability has been identified in SIMATIC S7-300 CPU family (All versions), SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 V6 and earlier CPU family (All versions), SIMATIC S7-400 V7 CPU family (All versions), SIMATIC S7-410 V8 CPU family (All versions), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants) (All versions). An attacker with network access to port 102/tcp (ISO-TSAP) or via Profibus could obtain credentials from the PLC if protection-level 2 is configured on the affected devices.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · high confidence

A credential disclosure vulnerability in SIMATIC S7-300 and S7-400 PLC families allows an unauthenticated remote attacker with network access to port 102/tcp (ISO-TSAP) or Profibus to obtain credentials when protection-level 2 is configured on the affected devices.

MitigationRestrict network access to port 102/tcp using firewalls or network segmentation, and upgrade to protection-level 3 or higher if available; consider applying vendor firmware updates and monitoring for unauthorized access attempts.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

Affected products & versions What the vendor confirmedThe version ranges the vendor confirmed as vulnerable. If your version sits inside a range here, treat yourself as exposed until you have upgraded.

NVD · CPE data
Simatic S7 300 Cpu FirmwareOperating system
Affected:all versions
Simatic S7 400 Cpu FirmwareOperating system
Affected:all versions

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
High
Privileges
None
User interaction
None
Scope
Unchanged
Confidentiality
High
Integrity
None
Availability
None

CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Identify PLC model
    Connect to the PLC via Step 7 (TIA Portal) or check device labeling/CMM module to confirm the device is a Simatic S7-300 or S7-400 CPU
    Affected if The device is a Simatic S7-300 or S7-400 CPU
  2. Check protection level configuration
    In Step 7 or TIA Portal, navigate to CPU properties > Protection > Protection Level, or use the 'PC Interface' function to read the device configuration and inspect the configured protection level
    Affected if Protection level 2 (read access) is configured; levels 0, 1, and 3 are not affected by this specific vulnerability
  3. Verify port 102/tcp accessibility
    From an external host, run 'nmap -p 102 <target-ip>' or use a TCP port scanner to check if port 102/tcp (ISO-TSAP) is open and reachable from the network
    Affected if Port 102/tcp is open and accessible from an untrusted network segment
  4. Check Profibus exposure
    If Profibus is used, verify whether the Profibus network is accessible from untrusted network segments or has gateway/proxy exposure
    Affected if Profibus interfaces are reachable from untrusted networks without segmentation

The device is affected if it is a Simatic S7-300 or S7-400 with protection level 2 configured AND port 102/tcp or Profibus is accessible from an untrusted network.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

From vendor data
Mitigation available No clean upgrade yet — mitigate in the meantime
Mitigation

Restrict network access to port 102/tcp using firewalls or network segmentation, and upgrade to protection-level 3 or higher if available; consider applying vendor firmware updates and monitoring for unauthorized access attempts.

Fix this in Simatic S7 300 Cpu Firmware Scoped from the published advisory
  • Consultation8.0 h
  • Implementation16.0 h
  • Testing12.0 h
  • Review / QA4.0 h
40.0 hours of engineering $7,000
Get help mitigating

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $11,200.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2016-9159 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2016-9159 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data