Modicon M241 FirmwareOperating system · Schneider Electric

CVE-2017-6030

MEDIUM · 6.5 CVSS v3.1 Published 2017-06-30
Fix available
A fix is available. Upgrade to after 4.0.3.20 or later.
See remediation →
74/100
Remediation priority · Elevated
Remotely reachable No privileges Zero-click

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
A predictable value range from previous values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial sequence numbers that may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · high confidence

Schneider Electric Modicon M221, M241, and M251 PLCs generate insufficiently random TCP initial sequence numbers, allowing attackers to predict ISN values from previous observations. This predictability enables TCP connection spoofing or disruption attacks against the PLC's network communications.

MitigationUpdate PLC firmware to Version 1.5.0.0 (M221) or Version 4.0.5.11 (M241/M251). If immediate patching is not feasible, implement network segmentation and firewall controls to limit exposure to untrusted networks.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

Affected products & versions What the vendor confirmedThe version ranges the vendor confirmed as vulnerable. If your version sits inside a range here, treat yourself as exposed until you have upgraded.

NVD · CPE data
Modicon M241 FirmwareOperating system
Affected:<= 4.0.3.20
Modicon M251 FirmwareOperating system
Affected:<= 4.0.3.20
Modicon M221 FirmwareOperating system
Affected:<= 1.1.1.5

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
Low
Privileges
None
User interaction
None
Scope
Unchanged
Confidentiality
None
Integrity
Low
Availability
Low

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:L

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Identify the Modicon PLC model
    Locate the PLC hardware label or check project configuration in SoMachine/EcoStruxure Machine Expert to confirm whether the device is an M221, M241, or M251 controller
    Affected if Device is not one of these three models (M221, M241, M251)
  2. Check the PLC firmware version
    Access the PLC via Schneider programming software (SoMachine/EcoStruxure Machine Expert), web interface, or console cable, then navigate to the firmware/version information screen to read the installed firmware build number
    Affected if Firmware version is <= 1.1.1.5 for M221, or <= 4.0.3.20 for M241 or M251
  3. Verify TCP/IP communication is enabled
    In the PLC programming software, expand the PLC configuration tree and check whether Ethernet, Modbus TCP, or other TCP-based communication services are configured and active
    Affected if TCP/IP stack is not present or completely disabled on the PLC
  4. Assess network accessibility of the PLC
    Review network architecture and firewall rules to determine whether the PLC's TCP ports (especially port 502 for Modbus/TCP) are exposed to untrusted or external networks
    Affected if PLC TCP ports are reachable from untrusted network segments or the internet

You are affected if you have a Modicon M221 with firmware <= 1.1.1.5, or an M241/M251 with firmware <= 4.0.3.20, and TCP/IP networking is enabled and accessible to potential attackers.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

From vendor data
Upgrade available Upgrade to a release after 4.0.3.20
Interim mitigation

Update PLC firmware to Version 1.5.0.0 (M221) or Version 4.0.5.11 (M241/M251). If immediate patching is not feasible, implement network segmentation and firewall controls to limit exposure to untrusted networks.

Fix this in Modicon M241 Firmware Scoped from the published advisory
  • Consultation6.0 h
  • Implementation12.0 h
  • Testing8.0 h
  • Review / QA4.0 h
30.0 hours of engineering $5,280
Get the upgrade done

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $8,448.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2017-6030 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2017-6030 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data