CVE-2018-7820
Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.
NVD · uneditedA Credentials Management CWE-255 vulnerability exists in the APC UPS Network Management Card 2 AOS v6.5.6, which could cause Remote Monitoring Credentials to be viewed in plaintext when Remote Monitoring is enabled, and then disabled.
Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.
dbcve analysis · high confidenceThe APC UPS Network Management Card 2 AOS v6.5.6 has a CWE-255 credentials management vulnerability where Remote Monitoring credentials are stored in plaintext and remain visible even after Remote Monitoring is disabled. When a user enables then disables the Remote Monitoring feature, the credentials are not properly cleared from memory/storage, allowing unauthorized disclosure of sensitive authentication credentials.
Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.
Affected products & versions What the vendor confirmedThe version ranges the vendor confirmed as vulnerable. If your version sits inside a range here, treat yourself as exposed until you have upgraded.
NVD · CPE data< 6.7.2< 6.7.2< 6.7.2< 6.7.2CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.
From the vector- Attack vector
- Network
- Complexity
- Low
- Privileges
- None
- User interaction
- None
- Scope
- Unchanged
- Confidentiality
- High
- Integrity
- High
- Availability
- High
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.
dbcve checksWork through these to decide whether this CVE applies to you.
-
Identify the firmware versionAccess the APC Network Management Card web interface and navigate to the About/Firmware Information page, or query via SNMP (snmpget on OID .1.3.6.1.4.1.318.1.1.1.1.1.1.0). Compare the displayed firmware version to 6.7.2.Affected if The installed firmware version is less than 6.7.2.
-
Check if Remote Monitoring was ever enabledAccess the Network Management Card web interface and navigate to the Remote Monitoring configuration section. Look for the current status and any history indicating the feature was previously enabled.Affected if Remote Monitoring was enabled at any point, regardless of current enabled/disabled state.
-
Verify credential visibilityIn the Network Management Card web interface, go to the Remote Monitoring or Network settings and examine whether the stored credentials (username/password) are visible in plaintext after disabling the feature.Affected if Credentials are visible in plaintext after Remote Monitoring has been disabled.
-
Check for credential persistence in backup/config exportsIf configuration backups are available, examine any exported configuration files or backups for plaintext credential storage. These may contain residual Remote Monitoring credentials.Affected if Backup or configuration files contain plaintext credentials that should have been cleared.
You are affected if your firmware version is below 6.7.2 and Remote Monitoring was ever enabled, with credentials remaining visible in plaintext after disabling the feature.
Generated from the published advisory. Verify against your own configuration.
Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.
dbcve · scoped6.7.2
Apply the vendor-supplied firmware patch for AOS v6.5.6 to remediate the plaintext credential storage issue. As a compensating control, ensure Remote Monitoring is only enabled when actively needed and consider rotating credentials after any instance of enabling/disabling this feature.
Firmware version 6.7.2 or later for Ap9630, Ap9631, Ap9635, and Smart UPS SRT 5kva
- Download APC Network Management Card firmware version 6.7.2 or later from the official APC website (www.apc.com)
- Access the NMC web interface for the affected device (Ap9630, Ap9631, Ap9635, or Smart UPS SRT 5kva)
- Navigate to the Firmware Update or Administration section in the web UI
- Upload and apply the firmware version 6.7.2 or later
- After the device reboots, verify the new firmware version is installed
- Confirm that Remote Monitoring credentials are no longer exposed in plaintext after toggling the Remote Monitoring setting
Generated from the published advisory — verify against the referenced sources before acting.
- Consultation4.0 h
- Implementation2.0 h
- Testing4.0 h
- Review / QA2.0 h
An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $3,392.
Scan for this in your stack
Free · runs locallyCheck whether your project pulls in CVE-2018-7820 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.
References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.
Primary sourcesPractitioner notes
ContributedPeer-ranked notes from engineers who’ve handled CVE-2018-7820 in production — separate from our analysis above.
The advisory tells you what broke. It rarely tells you what actually worked. If you’ve dealt with this one, that detail is what the next engineer is searching for.
- The version that genuinely resolved it — not the one the vendor claimed
- A config change or rule that shut the vector down
- A gotcha in the upgrade path that cost you an afternoon
No notes yet
Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.
A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.
- Verified mitigations, workarounds, and config changes
- Version or environment caveats, and links to real fixes
- No weaponised exploit code, or anything meant to cause harm
- No spam, self-promotion, credentials, or personal data