Pfc 200 FirmwareOperating system · Wago

CVE-2019-5080

CRITICAL · 9.1 CVSS v3.1 Published 2019-12-18
Mitigation only
No fix yet — a mitigation exists. There is no fixed release. A documented workaround reduces exposure in the meantime.
See remediation →
100/100
Remediation priority · Urgent
Remotely reachable No privileges Zero-click

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
An exploitable denial-of-service vulnerability exists in the iocheckd service "I/O-Check" functionality of WAGO PFC 200 Firmware versions 03.01.07(13) and 03.00.39(12), and WAGO PFC100 Firmware version 03.00.39(12). A single packet can cause a denial of service and weaken credentials resulting in the default documented credentials being applied to the device. An attacker can send an unauthenticated packet to trigger this vulnerability.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · moderate confidence

A denial-of-service vulnerability exists in the iocheckd service 'I/O-Check' functionality of WAGO PFC 200 and PFC100 programmable logic controllers. An unauthenticated attacker can send a single packet to trigger this vulnerability, causing denial of service and weakening device credentials to default documented values.

MitigationApply available firmware updates from WAGO; if patches are unavailable, isolate affected devices on a restricted network segment and monitor for unauthorized access attempts using the default credentials.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

Affected products & versions What the vendor confirmedThe version ranges the vendor confirmed as vulnerable. If your version sits inside a range here, treat yourself as exposed until you have upgraded.

NVD · CPE data
Pfc 200 FirmwareOperating system
Affected:= 03.00.39\(12\)= 03.01.07\(13\)
Pfc 100 FirmwareOperating system
Affected:= 03.00.39\(12\)

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
Low
Privileges
None
User interaction
None
Scope
Unchanged
Confidentiality
None
Integrity
High
Availability
High

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Identify WAGO PLC model
    Access the device web interface or check the device label to determine if it is a PFC 200 or PFC100 programmable logic controller.
    Affected if The device is a WAGO PFC 200 or PFC100 PLC.
  2. Check firmware version
    Access the device web interface and navigate to the firmware version information page, or use the WAGO e!COCKPIT software to query the device firmware version.
    Affected if The firmware version matches 03.00.39(12) or 03.01.07(13) for PFC200, or 03.00.39(12) for PFC100.
  3. Verify iocheckd service status
    Access the device via SSH or the Linux command line and check if the iocheckd service is running using the command: systemctl status iocheckd or check process status.
    Affected if The iocheckd service 'I/O-Check' is running on the device.
  4. Assess network exposure
    Review network configuration and firewall rules to determine if the iocheckd service ports are accessible from untrusted networks. The service typically listens on port 6626/tcp.
    Affected if The iocheckd service is accessible from an untrusted or external network without proper network segmentation.

You are affected if you have a WAGO PFC 200 or PFC100 device running an affected firmware version with the iocheckd service exposed to an untrusted network.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

From vendor data
Mitigation available No clean upgrade yet — mitigate in the meantime
Mitigation

Apply available firmware updates from WAGO; if patches are unavailable, isolate affected devices on a restricted network segment and monitor for unauthorized access attempts using the default credentials.

Fix this in Pfc 200 Firmware Scoped from the published advisory
  • Consultation4.0 h
  • Implementation8.0 h
  • Testing6.0 h
  • Review / QA4.0 h
22.0 hours of engineering $3,860
Get help mitigating

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $6,176.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2019-5080 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2019-5080 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data