Modicon Quantum 140noe77101 FirmwareOperating system · Schneider Electric

CVE-2019-6811

HIGH · 7.5 CVSS v3.1 Published 2019-09-17
Fix available
A fix is available. Upgrade to after 6.9 or later.
See remediation →
84/100
Remediation priority · High
Remotely reachable No privileges Zero-click

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
An Improper Check for Unusual or Exceptional Conditions (CWE-754) vulnerability exists in Modicon Quantum 140 NOE771x1 version 6.9 and earlier, which could cause denial of service when the module receives an IP fragmented packet with a length greater than 65535 bytes. The module then requires a power cycle to recover.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · high confidence

A CWE-754 (Improper Check for Unusual or Exceptional Conditions) vulnerability in the Modicon Quantum 140 NOE771x1 network module versions 6.9 and earlier allows denial of service when the module processes a specially crafted IP fragmented packet with a length exceeding 65535 bytes. The device enters an unrecoverable fault state requiring a power cycle to restore functionality.

MitigationApply the vendor-supplied firmware update when available, and implement network segmentation/firewall rules to filter malformed IP fragments exceeding 65535 bytes and limit exposure of affected industrial network modules to untrusted networks.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

Affected products & versions What the vendor confirmedThe version ranges the vendor confirmed as vulnerable. If your version sits inside a range here, treat yourself as exposed until you have upgraded.

NVD · CPE data
Modicon Quantum 140noe77101 FirmwareOperating system
Affected:<= 6.9
Modicon Quantum 140noe77111 FirmwareOperating system
Affected:<= 6.9

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
Low
Privileges
None
User interaction
None
Scope
Unchanged
Confidentiality
None
Integrity
None
Availability
High

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Identify the Modicon Quantum network module model
    Locate the physical hardware or check the device inventory for a Schneider Electric Modicon Quantum 140 NOE77101 or 140 NOE77111 network module. The model number is typically printed on the device label or visible in the network management interface.
    Affected if The model is 140 NOE77101 or 140 NOE77111
  2. Check the installed firmware version
    Access the network module through its web interface, management console, or Schneider Electric management software (such as Unity Pro or EcoStruxure). Navigate to the firmware version information page. Compare the displayed version against 6.9.
    Affected if The firmware version is 6.9 or earlier
  3. Verify network accessibility of the affected module
    Determine if the module is directly accessible from network segments that contain untrusted or external traffic. Check firewall rules, VLAN configurations, and network segmentation policies around the industrial network where the module is deployed.
    Affected if The module is reachable from untrusted network segments without filtering of malformed IP fragments

You are affected if you have a Modicon Quantum 140 NOE77101 or 140 NOE77111 network module running firmware version 6.9 or earlier that is network-accessible to potential attackers.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

From vendor data
Upgrade available Upgrade to a release after 6.9
Interim mitigation

Apply the vendor-supplied firmware update when available, and implement network segmentation/firewall rules to filter malformed IP fragments exceeding 65535 bytes and limit exposure of affected industrial network modules to untrusted networks.

Fix this in Modicon Quantum 140noe77101 Firmware Scoped from the published advisory
  • Consultation6.0 h
  • Implementation12.0 h
  • Testing6.0 h
  • Review / QA3.0 h
27.0 hours of engineering $4,800
Get the upgrade done

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $7,680.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2019-6811 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2019-6811 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data