Andover Continuum 9680 FirmwareOperating system · Schneider Electric

CVE-2020-7480

CRITICAL · 9.8 CVSS v3.1 Published 2020-03-23
Mitigation only
No fix yet — a mitigation exists. There is no fixed release. A documented workaround reduces exposure in the meantime.
See remediation →
100/100
Remediation priority · Urgent
Remotely reachable No privileges Zero-click

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
A CWE-94: Improper Control of Generation of Code ('Code Injection') vulnerability exists in Andover Continuum (All versions), which could cause files on the application server filesystem to be viewable when an attacker interferes with an application's processing of XML data.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · moderate confidence

A CWE-94 Code Injection vulnerability in Andover Continuum (all versions) allows attackers to view files on the application server filesystem through manipulation of XML data processing. The improper control of code generation during XML parsing enables unauthenticated file disclosure with critical severity (CVSS 9.8).

MitigationSince all versions are affected, contact the vendor for an available patch. Implement strict input validation and sanitization on XML data processing pathways, and restrict XML parser permissions to minimize filesystem access exposure.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

Affected products & versions What the vendor confirmedThe version ranges the vendor confirmed as vulnerable. If your version sits inside a range here, treat yourself as exposed until you have upgraded.

NVD · CPE data
Andover Continuum 9680 FirmwareOperating system
Affected:all versions
Andover Continuum 5740 FirmwareOperating system
Affected:all versions
Andover Continuum 5720 FirmwareOperating system
Affected:all versions
Andover Continuum Bcx4040 FirmwareOperating system
Affected:all versions
Andover Continuum Bcx9640 FirmwareOperating system
Affected:all versions
Andover Continuum 9900 FirmwareOperating system
Affected:all versions
Andover Continuum 9940 FirmwareOperating system
Affected:all versions
Andover Continuum 9941 FirmwareOperating system
Affected:all versions

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
Low
Privileges
None
User interaction
None
Scope
Unchanged
Confidentiality
High
Integrity
High
Availability
High

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Confirm Andover Continuum installation
    Identify if Schneider Electric Andover Continuum software is installed on the system by checking for the application directory, service, or web server process typically running on port 80/443
    Affected if Andover Continuum software or web interface is found on the host
  2. Identify the Andover Continuum model
    Check the system inventory, firmware information, or web interface banner for the specific model number (9680, 5740, 5720, Bcx4040, Bcx9640, 9900, 9940, or 9941)
    Affected if The model matches any of the affected variants listed in the CVE
  3. Verify XML processing endpoint is exposed
    Check if the web interface XML handler is accessible by attempting to access common XML processing paths or reviewing web server configuration for XML parsing endpoints
    Affected if XML data processing functionality is accessible via the web interface
  4. Confirm network exposure of the web interface
    Determine if the Andover Continuum web server is reachable from the network by checking firewall rules, listening ports, and interface bindings (0.0.0.0 vs 127.0.0.1)
    Affected if The web interface is accessible from network segments beyond localhost

Any Andover Continuum system (any of the eight listed models) with an exposed web interface containing XML processing functionality is vulnerable, since all firmware versions are affected.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

From vendor data
Mitigation available No clean upgrade yet — mitigate in the meantime
Mitigation

Since all versions are affected, contact the vendor for an available patch. Implement strict input validation and sanitization on XML data processing pathways, and restrict XML parser permissions to minimize filesystem access exposure.

Fix this in Andover Continuum 9680 Firmware Scoped from the published advisory
  • Consultation6.0 h
  • Implementation12.0 h
  • Testing10.0 h
  • Review / QA4.0 h
32.0 hours of engineering $5,580
Get help mitigating

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $8,928.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2020-7480 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2020-7480 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data