G 50a FirmwareOperating system · Mitsubishi

CVE-2021-20593

HIGH · 7.1 CVSS v3.1 Published 2021-07-13
Fix available
A fix is available. Upgrade to after 7.09 or later.
See remediation →
77/100
Remediation priority · High
Remotely reachable Zero-click

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
Incorrect Implementation of Authentication Algorithm in Mitsubishi Electric Air Conditioning System/Centralized Controllers (G-50A Ver.2.50 to Ver. 3.35, GB-50A Ver.2.50 to Ver. 3.35, AG-150A-A Ver.3.20 and prior, AG-150A-J Ver.3.20 and prior, GB-50ADA-A Ver.3.20 and prior, GB-50ADA-J Ver.3.20 and prior, EB-50GU-A Ver 7.09 and prior, EB-50GU-J Ver 7.09 and prior, AE-200A Ver 7.93 and prior, AE-200E Ver 7.93 and prior, AE-50A Ver 7.93 and prior, AE-50E Ver 7.93 and prior, EW-50A Ver 7.93 and prior, EW-50E Ver 7.93 and prior, TE-200A Ver 7.93 and prior, TE-50A Ver 7.93 and prior, TW-50A Ver 7.93 and prior, CMS-RMD-J Ver.1.30 and prior) and Air Conditioning System/Expansion Controllers (PAC-YG50ECA Ver.2.20 and prior) allows a remote authenticated attacker to impersonate administrators to disclose configuration information of the air conditioning system and tamper information (e.g. operation information and configuration of air conditioning system) by exploiting this vulnerability.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · high confidence

Incorrect implementation of the authentication algorithm in Mitsubishi Electric HVAC controllers allows a remote authenticated attacker to bypass proper authorization and impersonate administrators. This enables disclosure of system configuration and tampering with operational settings.

MitigationApply vendor-supplied firmware updates for all affected models; until patches are available, implement network segmentation to restrict access to HVAC controllers and monitor for unauthorized administrative actions.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

Affected products & versions What the vendor confirmedThe version ranges the vendor confirmed as vulnerable. If your version sits inside a range here, treat yourself as exposed until you have upgraded.

NVD · CPE data
G 50a FirmwareOperating system
Affected:>= 2.50, <= 3.35
Gb 50a FirmwareOperating system
Affected:>= 2.50, <= 3.35
Ag 150a A FirmwareOperating system
Affected:<= 3.20
Ag 150a J FirmwareOperating system
Affected:<= 3.20
Gb 50ada A FirmwareOperating system
Affected:<= 3.20
Gb 50ada J FirmwareOperating system
Affected:<= 3.20
Eb 50gu A FirmwareOperating system
Affected:<= 7.09
Eb 50gu J FirmwareOperating system
Affected:<= 7.09

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
Low
Privileges
Low
User interaction
None
Scope
Unchanged
Confidentiality
Low
Integrity
High
Availability
None

CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:H/A:N

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Identify HVAC controller model and firmware version
    Access the device's web management interface or check the device label/display for the model number (G 50a, Gb 50a, AG 150a, Gb 50ada, or Eb 50gu) and navigate to the firmware version information page typically found under System Information, Maintenance, or About sections
    Affected if The model matches one of the affected products (G 50a, Gb 50a, AG 150a A/J, Gb 50ada A/J, or Eb 50gu A/J) AND the firmware version falls within the affected ranges (2.50-3.35 for G 50a/Gb 50a, <=3.20 for AG 150a/Gb 50ada, or <=7.09 for Eb 50gu)
  2. Verify if remote management interface is exposed
    Check your network configuration to determine if the HVAC controller's web interface or management ports (typically HTTP/HTTPS on ports 80/443 or vendor-specific ports) are accessible from external networks or the internet
    Affected if The management interface is accessible from untrusted networks without proper network segmentation or firewall restrictions
  3. Review administrator account activity logs
    Examine the device's built-in logging or audit logs for the HVAC controller, looking for administrative actions, configuration changes, or login events that originate from unexpected IP addresses or occur at unusual times, particularly actions related to user privilege changes or system configuration exports
    Affected if Logs show administrative actions performed by accounts that should not have had those privileges, or duplicate admin sessions occurring simultaneously
  4. Inspect user account configuration for anomalies
    Review the user management section of the HVAC controller to identify any unauthorized changes to administrative accounts, unexpected new admin accounts, or privilege escalations that were not initiated by legitimate administrators
    Affected if Unexpected administrative accounts exist or legitimate accounts show unauthorized privilege modifications

Your environment is affected if you operate any of the listed Mitsubishi HVAC controller models within the specified firmware version ranges and the device management interface is network-accessible to potential attackers.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

From vendor data
Upgrade available Upgrade to a release after 7.09
Interim mitigation

Apply vendor-supplied firmware updates for all affected models; until patches are available, implement network segmentation to restrict access to HVAC controllers and monitor for unauthorized administrative actions.

Fix this in G 50a Firmware Scoped from the published advisory
  • Consultation8.0 h
  • Implementation16.0 h
  • Testing12.0 h
  • Review / QA8.0 h
44.0 hours of engineering $7,720
Get the upgrade done

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $12,352.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2021-20593 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2021-20593 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data