CVE-2021-31884
Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.
NVD · uneditedA vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.4), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.19), APOGEE PXC Modular (BACnet) (All versions < V3.5.4), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.19), Capital VSTAR (All versions with enabled Ethernet options), Desigo PXC00-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC00-U (All versions >= V2.3 and < V6.30.016), Desigo PXC001-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC100-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC12-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC128-U (All versions >= V2.3 and < V6.30.016), Desigo PXC200-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC22.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC36.1-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC50-E.D (All versions >= V2.3 and < V6.30.016), Desigo PXC64-U (All versions >= V2.3 and < V6.30.016), Desigo PXM20-E (All versions >= V2.3 and < V6.30.016), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.4), Nucleus Source Code (All versions), TALON TC Compact (BACnet) (All versions < V3.5.4), TALON TC Modular (BACnet) (All versions < V3.5.4). The DHCP client application assumes that the data supplied with the “Hostname” DHCP option is NULL terminated. In cases when global hostname variable is not defined, this may lead to Out-of-bound reads, writes, and Denial-of-service conditions. (FSMD-2021-0014)
Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.
dbcve analysis · high confidenceThe DHCP client application in multiple Siemens building automation controllers and Nucleus RTOS does not properly validate the length of the Hostname DHCP option, assuming it is NULL-terminated. When the global hostname variable is undefined, this causes out-of-bounds memory reads and writes, leading to potential code execution and denial-of-service conditions.
Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.
Affected products & versions What the vendor confirmedThe version ranges the vendor confirmed as vulnerable. If your version sits inside a range here, treat yourself as exposed until you have upgraded.
NVD · CPE dataall versionsall versions< 2017.02.1all versionsall versionsall versions< 2.8.19< 3.5.4< 2.8.19< 3.5.4CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.
From the vector- Attack vector
- Network
- Complexity
- Low
- Privileges
- None
- User interaction
- None
- Scope
- Unchanged
- Confidentiality
- High
- Integrity
- High
- Availability
- High
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.
dbcve checksWork through these to decide whether this CVE applies to you.
-
Identify the device firmware or software product and versionAccess the device management interface, web UI, or system information to determine the exact firmware version (e.g., Apogee PXC Compact, PXC Modular) or software version (e.g., Nucleus Readystart V3). Compare against the affected version ranges provided.Affected if The product is any of: Siemens Capital Vstar (any version), Siemens Nucleus Net (any version), Nucleus Readystart V3 (version below 2017.02.1), Nucleus Source Code (any version), Apogee Modular Building Controller (any version), Apogee Modular Equipment Controller (any version), Apogee PXC Compact (
-
Determine whether DHCP client is enabledCheck the network configuration settings on the device or controller. Look for DHCP client settings in the network/IP configuration menu, web interface, or configuration files. Confirm if DHCP is set to 'enabled' or if the device is configured to obtain IP address automatically.Affected if DHCP client is enabled on the device, as this is the attack vector for sending malicious Hostname DHCP options to the client.
-
Verify hostname configuration statusCheck the DHCP client hostname or system hostname configuration setting on the device. Determine whether the global hostname variable is defined/configured or left undefined/blank in the DHCP client settings.Affected if The hostname variable is undefined, blank, or not explicitly configured in the DHCP client settings, which is the specific condition that triggers the out-of-bounds memory access.
The device is affected if it runs any of the affected product versions AND uses DHCP client with an undefined hostname configuration, allowing a malicious DHCP server to exploit the unsanitized Hostname option length.
Generated from the published advisory. Verify against your own configuration.
Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.
From vendor data2.8.193.5.42017.02.1
Apply vendor firmware updates where available (APOGEE PXC and TALON require V3.5.4 or later for BACnet, V2.8.19 or later for P2 Ethernet; Desigo requires V6.30.016 or later). For unpatched devices, isolate on a dedicated network segment and consider using static IP addressing instead of DHCP to avoid processing malicious hostname options.
- Consultation8.0 h
- Implementation16.0 h
- Testing12.0 h
- Review / QA8.0 h
An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $12,352.
Scan for this in your stack
Free · runs locallyCheck whether your project pulls in CVE-2021-31884 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.
References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.
Primary sourcesPractitioner notes
ContributedPeer-ranked notes from engineers who’ve handled CVE-2021-31884 in production — separate from our analysis above.
The advisory tells you what broke. It rarely tells you what actually worked. If you’ve dealt with this one, that detail is what the next engineer is searching for.
- The version that genuinely resolved it — not the one the vendor claimed
- A config change or rule that shut the vector down
- A gotcha in the upgrade path that cost you an afternoon
No notes yet
Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.
A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.
- Verified mitigations, workarounds, and config changes
- Version or environment caveats, and links to real fixes
- No weaponised exploit code, or anything meant to cause harm
- No spam, self-promotion, credentials, or personal data