Interactive Graphical Scada SystemApplication · Schneider Electric

CVE-2022-32523

CRITICAL · 9.8 CVSS v3.1 Published 2023-01-30
Fix available
A fix is available. Upgrade to after 15.0.0.22170 or later.
See remediation →
100/100
Remediation priority · Urgent
Remotely reachable No privileges Zero-click Patch available

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow, potentially leading to remote code execution when an attacker sends specially crafted online data request messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170)

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis
How this class of weakness works · CWE-120

A fixed-size buffer is filled without checking the length of the incoming data, so it overflows into neighbouring memory. This is the classic overflow attackers use to overwrite return addresses and hijack execution. The fix is strict length checks and safe, bounded string and memory functions.

General guidance for the classic buffer overflow class — the official description and references above are authoritative for this specific CVE. Want a bespoke review and a reviewed fix? Ask our team →

Affected products & versions What the vendor confirmedThe version ranges the vendor confirmed as vulnerable. If your version sits inside a range here, treat yourself as exposed until you have upgraded.

NVD · CPE data
Interactive Graphical Scada SystemApplication
Affected:<= 15.0.0.22170

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
Low
Privileges
None
User interaction
None
Scope
Unchanged
Confidentiality
High
Integrity
High
Availability
High

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

dbcve · scoped
Upgrade available Upgrade to a release after 15.0.0.22170
Recommended fix High confidence

IGSS V15.0.0.22170 or later

  1. 1. Identify all IGSS Data Server installations (IGSSdataServer.exe) in the environment and note their current versions.
  2. 2. Download the security patch from the vendor reference: https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2022-165-01_IGSS_Security_Notification_V2.pdf
  3. 3. Review the patch release notes to confirm it contains the fix for CVE-2022-32523 (CWE-120 buffer overflow).
  4. 4. Create a backup of the current IGSS configuration and database files before applying the update.
  5. 5. Apply version 15.0.0.22170 or later of IGSS Data Server to all affected installations.
  6. 6. Verify the installed version matches the target (15.0.0.22170 or higher).
  7. 7. Restart the IGSS Data Server service to ensure the patched code is loaded.
  8. 8. Test critical IGSS functionality to confirm normal operations after patching.

Generated from the published advisory — verify against the referenced sources before acting.

We can identify the exact fixed release, upgrade, and verify it in staging — typical engagement from $3,550. Get the upgrade done

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2022-32523 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2022-32523 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data