Gt Softgot2000Application · Mitsubishielectric

CVE-2022-40269

HIGH · 8.1 CVSS v3.1 Published 2023-02-02
Fix available
A fix is available. Upgrade to 01.48.000 / 1.290c or later.
See remediation →
88/100
Remediation priority · High
Remotely reachable No privileges

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
Authentication Bypass by Spoofing vulnerability in Mitsubishi Electric Corporation GOT2000 Series GT27 model versions 01.14.000 to 01.47.000, Mitsubishi Electric Corporation GOT2000 Series GT25 model versions 01.14.000 to 01.47.000 and Mitsubishi Electric Corporation GT SoftGOT2000 versions 1.265B to 1.285X allows a remote unauthenticated attacker to disclose sensitive information from users' browsers or spoof legitimate users by abusing inappropriate HTML attributes.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · high confidence

Authentication bypass by spoofing vulnerability in Mitsubishi Electric GOT2000 Series HMI products allows remote unauthenticated attackers to disclose sensitive information from users' browsers or spoof legitimate users by abusing inappropriate HTML attributes in the web interface.

MitigationApply vendor-supplied patches to update to versions beyond 01.47.000 for GT27/GT25 and beyond 1.285X for SoftGOT2000; until patched, limit network exposure and monitor for suspicious access patterns.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

Affected products & versions What the vendor confirmedThe version ranges the vendor confirmed as vulnerable. If your version sits inside a range here, treat yourself as exposed until you have upgraded.

NVD · CPE data
Gt Softgot2000Application
Affected:>= 1.265b, < 1.290c
Gt27 FirmwareOperating system
Affected:>= 01.14.000, < 01.48.000
Gt25 FirmwareOperating system
Affected:>= 01.14.000, < 01.48.000

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
Low
Privileges
None
User interaction
Required
Scope
Unchanged
Confidentiality
High
Integrity
High
Availability
None

CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:N

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Identify the GOT2000 product type
    Determine if the system uses GT SoftGOT2000 software, GT27 hardware, or GT25 hardware. Check software installations or hardware labels on the HMI device.
    Affected if The product is any of these three: GT SoftGOT2000, GT27, or GT25
  2. Check GT SoftGOT2000 version
    Open GT SoftGOT2000, navigate to Help > Version Information, or check the software's about dialog to find the exact version number (format like 1.XXXc).
    Affected if Version is >= 1.265b and < 1.290c
  3. Check GT27/GT25 firmware version
    On the HMI device, access System Information from the utility menu, or use GT Designer3 software to connect and read the firmware version (format like 01.XX.XXX).
    Affected if Firmware version is >= 01.14.000 and < 01.48.000
  4. Verify web interface is enabled
    Check if the HMI's web server or remote access feature is configured and active. For SoftGOT2000, verify if the virtual GOT web functions are enabled. For hardware GOT, check if Ethernet/web functions are enabled in the device settings.
    Affected if The web interface is accessible over the network (the vulnerability requires the web interface to be exposed)

The system is affected if it runs any GT SoftGOT2000 version >= 1.265b and < 1.290c, or GT27/GT25 firmware >= 01.14.000 and < 01.48.000, AND the web interface is enabled and network-accessible.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

dbcve · scoped
Upgrade available Upgrade to 01.48.000 / 1.290c or later
Fixed in 01.48.0001.290c
Interim mitigation

Apply vendor-supplied patches to update to versions beyond 01.47.000 for GT27/GT25 and beyond 1.285X for SoftGOT2000; until patched, limit network exposure and monitor for suspicious access patterns.

Recommended fix High confidence

GT27/GT25 firmware: 01.48.000 or later | GT SoftGOT2000: 1.290c or later

  1. Identify the exact installed version of Mitsubishi Electric GOT2000 Series (GT27 or GT25) firmware or GT SoftGOT2000 software
  2. Navigate to the official Mitsubishi Electric download page for GOT2000 series firmware or GT SoftGOT2000 software
  3. Download the firmware version 01.48.000 or later for GT27/GT25, or version 1.290c or later for GT SoftGOT2000
  4. Follow the official Mitsubishi Electric firmware update procedure documented in the GOT2000 User's Manual
  5. Apply the firmware update to the GOT2000 device or update the GT SoftGOT2000 installation
  6. Verify the updated version matches or exceeds the fixed release (GT27/GT25: 01.48.000, GT SoftGOT2000: 1.290c)
Caveat Review Mitsubishi Electric firmware update documentation for any special update procedures or prerequisites; firmware updates may require device downtime

Generated from the published advisory — verify against the referenced sources before acting.

Fix this in Gt Softgot2000 Scoped from the published advisory
  • Consultation4.0 h
  • Implementation2.0 h
  • Testing6.0 h
  • Review / QA3.0 h
15.0 hours of engineering $2,600
Get the upgrade done

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $4,160.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2022-40269 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2022-40269 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data