VulnerabilityAwaiting classification

CVE-2024-12169

MEDIUM · 6.5 CVSS v3.1 Published 2025-03-25
Mitigation only
No fix yet — a mitigation exists. There is no fixed release. A documented workaround reduces exposure in the meantime.
See remediation →
71/100
Remediation priority · Elevated
Remotely reachable Zero-click

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
A vulnerability exists in RTU500 IEC 60870-5-104 controlled station functionality and IEC 61850 functionality, that allows an attacker performing a specific attack sequence to restart the affected CMU. This vulnerability only applies, if secure communication using IEC 62351-3 (TLS) is enabled.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · moderate confidence

Vulnerability in RTU500 CMU (Communication Management Unit) allows an attacker to trigger a restart of the device through a specific attack sequence against IEC 60870-5-104 or IEC 61850 protocol implementations when IEC 62351-3 (TLS) secure communication is enabled. This is a denial-of-service vulnerability targeting the protocol handling layer.

MitigationApply vendor-supplied firmware/patch when available. If patch is unavailable, evaluate risk acceptance or temporary workarounds per organizational security policy. The vulnerability is conditional on TLS being enabled, so impact scope may be limited to TLS-configured deployments.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
Low
Privileges
Low
User interaction
None
Scope
Unchanged
Confidentiality
None
Integrity
None
Availability
High

CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Confirm RTU500 CMU device type
    Identify the device model through system inventory, device labeling, or management interface. RTU500 CMU refers to the Communication Management Unit product line.
    Affected if The device is not an RTU500 CMU product, then it is not affected.
  2. Check firmware version
    Access the device management interface or use vendor-provided diagnostic tools to retrieve the current firmware version. Compare against any vendor-provided version guidance.
    Affected if Unable to confirm firmware version or version falls within any vendor-specified affected range.
  3. Verify IEC 62351-3 TLS is enabled
    Examine the device configuration for IEC 62351-3 (TLS) secure communication settings. This is typically found in protocol security or communication settings. Check configuration files or management GUI for TLS-enabled IEC 60870-5-104 or IEC 61850 connections.
    Affected if IEC 62351-3 (TLS) is disabled or not configured; the vulnerability requires TLS to be enabled to be exploitable.
  4. Confirm IEC 60870-5-104 or IEC 61850 protocol usage
    Review the device protocol configuration to identify active IEC 60870-5-104 or IEC 61850 protocol instances. Check connection settings, protocol bindings, or enabled protocol list.
    Affected if Neither IEC 60870-5-104 nor IEC 61850 protocols are configured or enabled on the device.
  5. Check for restart events
    Review system logs, event logs, or device uptime records for unexpected restarts or crashes, particularly correlated with IEC 60870-5-104 or IEC 61850 protocol activity.
    Affected if Device has experienced unexplained restarts or denial-of-service conditions without other identified cause.

If the device is an RTU500 CMU with IEC 62351-3 (TLS) enabled for IEC 60870-5-104 or IEC 61850 protocols, the environment matches the vulnerability conditions and may be affected.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

From vendor data
Mitigation available No clean upgrade yet — mitigate in the meantime
Mitigation

Apply vendor-supplied firmware/patch when available. If patch is unavailable, evaluate risk acceptance or temporary workarounds per organizational security policy. The vulnerability is conditional on TLS being enabled, so impact scope may be limited to TLS-configured deployments.

Have this fixed Scoped from the published advisory
  • Consultation5.0 h
  • Implementation3.0 h
  • Testing4.0 h
  • Review / QA3.0 h
15.0 hours of engineering $2,680
Get help mitigating

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $4,288.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2024-12169 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2024-12169 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm