CVE-2024-53649
Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.
NVD · uneditedA vulnerability has been identified in SIPROTEC 5 6MD84 (CP300) (All versions < V9.80), SIPROTEC 5 6MD85 (CP300) (All versions >= V7.80 < V9.80), SIPROTEC 5 6MD86 (CP300) (All versions >= V7.80 < V9.80), SIPROTEC 5 6MD89 (CP300) (All versions >= V7.80 < V9.68), SIPROTEC 5 6MU85 (CP300) (All versions >= V7.80 < V9.80), SIPROTEC 5 7KE85 (CP300) (All versions >= V7.80 < V9.80), SIPROTEC 5 7SA82 (CP100) (All versions >= V7.80 < V8.90), SIPROTEC 5 7SA82 (CP150) (All versions < V9.80), SIPROTEC 5 7SA86 (CP300) (All versions >= V7.80 < V9.80), SIPROTEC 5 7SA87 (CP300) (All versions >= V7.80 < V9.80), SIPROTEC 5 7SD82 (CP100) (All versions >= V7.80 < V8.90), SIPROTEC 5 7SD82 (CP150) (All versions < V9.80), SIPROTEC 5 7SD86 (CP300) (All versions >= V7.80 < V9.80), SIPROTEC 5 7SD87 (CP300) (All versions >= V7.80 < V9.80), SIPROTEC 5 7SJ81 (CP100) (All versions >= V7.80 < V8.90), SIPROTEC 5 7SJ81 (CP150) (All versions < V9.80), SIPROTEC 5 7SJ82 (CP100) (All versions >= V7.80 < V8.90), SIPROTEC 5 7SJ82 (CP150) (All versions < V9.80), SIPROTEC 5 7SJ85 (CP300) (All versions >= V7.80 < V9.80), SIPROTEC 5 7SJ86 (CP300) (All versions >= V7.80 < V9.80), SIPROTEC 5 7SK82 (CP100) (All versions >= V7.80 < V8.90), SIPROTEC 5 7SK82 (CP150) (All versions < V9.80), SIPROTEC 5 7SK85 (CP300) (All versions >= V7.80 < V9.80), SIPROTEC 5 7SL82 (CP100) (All versions >= V7.80 < V8.90), SIPROTEC 5 7SL82 (CP150) (All versions < V9.80), SIPROTEC 5 7SL86 (CP300) (All versions >= V7.80 < V9.80), SIPROTEC 5 7SL87 (CP300) (All versions >= V7.80 < V9.80), SIPROTEC 5 7SS85 (CP300) (All versions >= V7.80 < V9.80), SIPROTEC 5 7ST85 (CP300) (All versions < V9.68), SIPROTEC 5 7ST86 (CP300) (All versions < V9.80), SIPROTEC 5 7SX82 (CP150) (All versions < V9.80), SIPROTEC 5 7SX85 (CP300) (All versions < V9.80), SIPROTEC 5 7SY82 (CP150) (All versions < V9.80), SIPROTEC 5 7UM85 (CP300) (All versions >= V7.80 < V9.80), SIPROTEC 5 7UT82 (CP100) (All versions >= V7.80 < V8.90), SIPROTEC 5 7UT82 (CP150) (All versions < V9.80), SIPROTEC 5 7UT85 (CP300) (All versions >= V7.80 < V9.80), SIPROTEC 5 7UT86 (CP300) (All versions >= V7.80 < V9.80), SIPROTEC 5 7UT87 (CP300) (All versions >= V7.80 < V9.80), SIPROTEC 5 7VE85 (CP300) (All versions >= V7.80 < V9.80), SIPROTEC 5 7VK87 (CP300) (All versions >= V7.80 < V9.80), SIPROTEC 5 7VU85 (CP300) (All versions < V9.80), SIPROTEC 5 Compact 7SX800 (CP050) (All versions < V9.80). Affected devices do not properly limit the path accessible via their webserver. This could allow an authenticated remote attacker to read arbitrary files from the filesystem of affected devices.
Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.
dbcve analysis · high confidenceSIPROTEC 5 protection devices contain a path traversal vulnerability in their embedded webserver. An authenticated remote attacker can manipulate path parameters to access files outside the intended webroot directory, potentially exposing sensitive system files, configuration data, or credentials.
Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.
CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.
From the vector- Attack vector
- Network
- Complexity
- Low
- Privileges
- Low
- User interaction
- None
- Scope
- Unchanged
- Confidentiality
- High
- Integrity
- None
- Availability
- None
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N
Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.
dbcve checksWork through these to decide whether this CVE applies to you.
-
Confirm device is a SIPROTEC 5 protection deviceIdentify the device model number (typically found on device label, web interface header, or via SNMP/sysinfo query). Look for SIPROTEC 5 series designations such as 7UT75, 7UT85, 6MD89, 7ST85, or similar model numbers in the SIPROTEC 5 family.Affected if The device model number matches the SIPROTEC 5 product line (e.g., 7xxx or 6xxx series protection devices from Siemens).
-
Determine the firmware or webserver versionAccess the device web interface and navigate to the About, System Info, or Device Info page (typically under Setup or Maintenance menu). Alternatively, query the device via SNMP or serial console using vendor-specific OIDs or commands to retrieve firmware version.Affected if The installed firmware version is earlier than V9.68 (for 6MD89/7ST85 models) or earlier than V9.80 (for other SIPROTEC 5 models).
-
Verify the embedded webserver is enabledCheck the device configuration via web interface (under Communication Settings or HTTP Server settings) or via serial console. Confirm whether the HTTP/HTTPS webserver service is actively running.Affected if The webserver interface is enabled and accessible on the device.
-
Check webserver network exposureReview network configuration to determine if the webserver is bound to external/network-accessible interfaces (as opposed to localhost-only or internal VLAN). Inspect firewall rules or access control lists that govern webserver reachability.Affected if The webserver is reachable from network segments beyond the trusted management network.
-
Verify authentication configurationInspect the webserver authentication settings in the device configuration. Confirm whether local user accounts, LDAP integration, or other authentication mechanisms are configured and enabled for web access.Affected if Authentication is enabled for the web interface (which is required for the vulnerability to be exploitable).
The environment is affected if it is a SIPROTEC 5 device with webserver enabled, accessible over the network, running firmware versions prior to V9.68 (6MD89/7ST85) or V9.80 (other models), and authentication is configured.
Generated from the published advisory. Verify against your own configuration.
Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.
dbcve · scopedUpgrade affected SIPROTEC 5 devices to the patched version (V9.80 or later per model, V9.68 for 6MD89 and 7ST85). If immediate patching is not feasible, restrict network access to the webserver interface and enforce strong authentication.
Firmware V9.80 or later (or V9.68+ for 6MD89 and 7ST85 models)
- Identify the specific SIPROTEC 5 device model and CPU type (CP300, CP150, CP100, or CP050) from the product label or firmware
- Access the Siemens Industry Online Support portal at https://support.industry.siemens.com/ or contact Siemens customer support to obtain the firmware upgrade
- Download the firmware version V9.80 or later for your device model (or V9.68 for SIPROTEC 5 6MD84, 6MD89, 7ST85, or 7ST86 if V9.80 is not available)
- Review the Siemens firmware upgrade instructions for SIPROTEC 5 devices in the product manual
- Ensure the device is in a safe operational state and backup current configuration if possible
- Upload and install the new firmware version via the device's web interface or engineering tool (e.g., DIGSI 5)
- After upgrade, verify the firmware version matches the target fixed version
- Confirm the webserver path limitation has been addressed by testing that arbitrary filesystem paths are no longer accessible
Generated from the published advisory — verify against the referenced sources before acting.
- Consultation4.0 h
- Implementation8.0 h
- Testing6.0 h
- Review / QA4.0 h
An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $6,176.
Scan for this in your stack
Free · runs locallyCheck whether your project pulls in CVE-2024-53649 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.
References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.
Primary sourcesPractitioner notes
ContributedPeer-ranked notes from engineers who’ve handled CVE-2024-53649 in production — separate from our analysis above.
The advisory tells you what broke. It rarely tells you what actually worked. If you’ve dealt with this one, that detail is what the next engineer is searching for.
- The version that genuinely resolved it — not the one the vendor claimed
- A config change or rule that shut the vector down
- A gotcha in the upgrade path that cost you an afternoon
No notes yet
Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.
A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.
- Verified mitigations, workarounds, and config changes
- Version or environment caveats, and links to real fixes
- No weaponised exploit code, or anything meant to cause harm
- No spam, self-promotion, credentials, or personal data