CVE-2024-54089
Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.
NVD · uneditedA vulnerability has been identified in APOGEE PXC Series (BACnet) (All versions), APOGEE PXC Series (P2 Ethernet) (All versions), TALON TC Series (BACnet) (All versions). Affected devices contain a weak encryption mechanism based on a hard-coded key. This could allow an attacker to guess or decrypt the password from the cyphertext.
Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.
dbcve analysis · high confidenceHard-coded cryptographic keys in APOGEE PXC and TALON TC Series building automation controllers allow attackers to decrypt stored passwords from captured ciphertext. The weak encryption mechanism uses a static key embedded in firmware, enabling credential recovery and subsequent unauthorized access to the BACnet/P2 Ethernet networks.
Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.
CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.
From the vector- Attack vector
- Network
- Complexity
- Low
- Privileges
- None
- User interaction
- None
- Scope
- Unchanged
- Confidentiality
- High
- Integrity
- None
- Availability
- None
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.
dbcve checksWork through these to decide whether this CVE applies to you.
-
Identify device modelLocate the device label, Web UI, or management interface to confirm the exact model number. Look for APOGEE PXC Series or TALON TC Series controllers.Affected if The device is an APOGEE PXC or TALON TC Series building automation controller.
-
Check firmware versionAccess the controller via its management interface, SNMP, or vendor tools to retrieve the installed firmware version. Compare against any vendor-released firmware advisories.Affected if The firmware version matches ranges or is prior to versions that address the hardcoded key issue.
-
Verify stored credentials existExamine the controller configuration for locally stored user accounts, passwords, or BACnet/P2 Ethernet network credentials. Check backup files, configuration exports, or the device Web interface for password fields.Affected if The device stores passwords or network credentials in encrypted form locally.
-
Inspect firmware for hardcoded keyIf firmware extraction is possible (via vendor tools, firmware dump, or firmware update file), examine the binary for static cryptographic key patterns or known weak encryption constants used in password storage.Affected if The firmware contains a hardcoded/static encryption key rather than per-device or user-derived keys.
-
Analyze captured network trafficReview any stored network packet captures (PCAP files) from BACnet/P2 Ethernet communications to identify transmitted credential data that may have been encrypted with the weak mechanism.Affected if Encrypted credentials transmitted over the network were captured and could be decrypted using the static key.
You are affected if you operate an APOGEE PXC or TALON TC Series controller that stores credentials encrypted with a hardcoded firmware-embedded key, particularly if those credentials or network traffic have been exposed.
Generated from the published advisory. Verify against your own configuration.
Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.
From vendor dataApply network segmentation and access controls to isolate affected devices; contact vendor for firmware updates addressing the hardcoded key; monitor for credential theft attempts; consider compensating controls until patches are available.
- Consultation8.0 h
- Implementation16.0 h
- Testing8.0 h
- Review / QA4.0 h
An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $10,240.
Scan for this in your stack
Free · runs locallyCheck whether your project pulls in CVE-2024-54089 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.
References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.
Primary sourcesPractitioner notes
ContributedPeer-ranked notes from engineers who’ve handled CVE-2024-54089 in production — separate from our analysis above.
The advisory tells you what broke. It rarely tells you what actually worked. If you’ve dealt with this one, that detail is what the next engineer is searching for.
- The version that genuinely resolved it — not the one the vendor claimed
- A config change or rule that shut the vector down
- A gotcha in the upgrade path that cost you an afternoon
No notes yet
Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.
A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.
- Verified mitigations, workarounds, and config changes
- Version or environment caveats, and links to real fixes
- No weaponised exploit code, or anything meant to cause harm
- No spam, self-promotion, credentials, or personal data