Controllogix 5580 FirmwareOperating system · Rockwellautomation

CVE-2024-6207

HIGH · 7.5 CVSS v3.1 Published 2024-10-14
Fix available
A fix is available. Upgrade to 33.017 / 34.014 or later.
See remediation →
84/100
Remediation priority · High
Remotely reachable No privileges Zero-click

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
CVE 2021-22681 https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.PN1550.html  and send a specially crafted CIP message to the device. If exploited, a threat actor could help prevent access to the legitimate user and end connections to connected devices including the workstation. To recover the controllers, a download is required which ends any process that the controller is running.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · moderate confidence

This is a denial of service vulnerability in Rockwell Automation controllers exploitable via specially crafted CIP (Common Industrial Protocol) messages. Successful exploitation prevents legitimate user access and disconnects connected devices including workstations. Recovery requires a controller download, which terminates all running processes.

MitigationImplement network segmentation to isolate industrial control systems, apply CIP message filtering at network boundaries, and review Rockwell Automation advisory PN1550 for specific device patches and hardening guidance.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

Affected products & versions What the vendor confirmedThe version ranges the vendor confirmed as vulnerable. If your version sits inside a range here, treat yourself as exposed until you have upgraded.

NVD · CPE data
Controllogix 5580 FirmwareOperating system
Affected:>= 28.011, < 33.017>= 34.011, < 34.014>= 35.011, < 35.013
Controllogix 5580 Process FirmwareOperating system
Affected:>= 33.011, < 33.017>= 34.011, < 34.014>= 35.011, < 35.013
Guardlogix 5580 FirmwareOperating system
Affected:>= 31.011, < 33.017>= 34.011, < 34.014>= 35.011, < 35.013
Compactlogix 5380 FirmwareOperating system
Affected:>= 28.011, < 33.017>= 34.011, < 34.014>= 35.011, < 35.013
Compact Guardlogix 5380 Sil 2 FirmwareOperating system
Affected:>= 31.011, < 33.017>= 34.011, < 34.014>= 35.011, < 35.013
Compact Guardlogix 5380 Sil 3 FirmwareOperating system
Affected:>= 32.013, < 33.017>= 34.011, < 34.014>= 35.011, < 35.013
Compactlogix 5480 FirmwareOperating system
Affected:>= 32.011, < 33.017>= 34.011, < 34.014>= 35.011, < 35.013
Factorytalk Logix Echo FirmwareOperating system
Affected:>= 33.011, < 34.014>= 35.011, < 35.013

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
Low
Privileges
None
User interaction
None
Scope
Unchanged
Confidentiality
None
Integrity
None
Availability
High

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Identify the controller model
    Determine the exact Rockwell Automation controller model in your environment (e.g., Controllogix 5580, Compactlogix 5380, Guardlogix 5580, Compactlogix 5480, or Factorytalk Logix Echo). Check controller labels, RSLinx Classic or FactoryTalk Linx device browser, or the controller's web-based interface.
    Affected if The controller model is one of the affected products listed in the CVE advisory.
  2. Retrieve the installed firmware version
    Access the controller firmware version via RSLinx Classic (right-click controller > Device Properties), FactoryTalk Linx, the controller's web interface (if available), or via Studio 5000 Logix Designer (go to Controller Properties > General).
    Affected if The firmware version falls within any of these ranges: >= 28.011 and < 33.017; >= 34.011 and < 34.014; >= 35.011 and < 35.013 (specific ranges vary by controller model).
  3. Verify CIP communication is enabled
    Check if the controller has CIP (Common Industrial Protocol) messaging enabled and is exposed to the network. In RSLinx Classic, verify the CIP driver (e.g., Ethernet/IP driver) is running and the controller is browsable. In FactoryTalk Linx, check the network topology for active CIP connections.
    Affected if CIP is enabled and the controller is network-accessible, making it reachable for specially crafted CIP messages.
  4. Assess network exposure
    Review network architecture to determine if the controller is directly accessible from less-trusted networks. Check firewall rules, VLAN configurations, and network segmentation around the industrial control system. Identify if the controller has an IP address on a network segment that could receive untrusted CIP traffic.
    Affected if The controller is accessible from network segments beyond the isolated industrial control environment, increasing exploitability.

You are affected if your controller is one of the affected models listed, runs a firmware version within the vulnerable ranges, and has CIP communication enabled and network-accessible.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

dbcve · scoped
Upgrade available Upgrade to 33.017 / 34.014 / 35.013 or later
Fixed in 33.01734.01435.013
Interim mitigation

Implement network segmentation to isolate industrial control systems, apply CIP message filtering at network boundaries, and review Rockwell Automation advisory PN1550 for specific device patches and hardening guidance.

Recommended fix High confidence

Firmware version 33.017 or later (or 34.014 or later, or 35.013 or later depending on the version track for your specific controller)

  1. 1. Identify the exact Controllogix/Guardlogix/Compactlogix controller model and current firmware version installed on the device
  2. 2. Navigate to the Rockwell Automation Product Compatibility and Download Center (PCDC) at https://compatibility.rockwellautomation.com/
  3. 3. Search for the specific controller model to find available firmware updates
  4. 4. Download firmware version 33.017 or later (or 34.014 or later, or 35.013 or later) that is compatible with your hardware revision
  5. 5. Review release notes for any special installation instructions or prerequisites
  6. 6. Backup controller project and configuration data before performing firmware update
  7. 7. Upload the current project from the controller to preserve logic and tags
  8. 8. Update firmware using RSLinx Classic or FactoryTalk Linx with ControlFLASH or ControlFLASH Plus utility
Caveat Firmware updates to controllers may require project re-download and can interrupt running processes; ensure proper backup and maintenance window is scheduled

Generated from the published advisory — verify against the referenced sources before acting.

Fix this in Controllogix 5580 Firmware Scoped from the published advisory
  • Consultation8.0 h
  • Implementation16.0 h
  • Testing12.0 h
  • Review / QA8.0 h
44.0 hours of engineering $7,720
Get the upgrade done

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $12,352.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2024-6207 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2024-6207 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data