CVE-2025-0657

HIGH · 8.8 CVSS v4.0 Published 2025-11-27
Mitigation only
No fix yet — a mitigation exists. There is no fixed release. A documented workaround reduces exposure in the meantime.
See remediation →
97/100
Remediation priority · Urgent
Remotely reachable No privileges Zero-click

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
A weakness in Automated Logic and Carrier i-Vu Gen5 router on driver version drv_gen5_106-01-2380, allows malformed packets to be sent through BACnet MS/TP network causing the devices to enter a fault state. This fault state requires a manual power cycle to return the device to network visibility.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · high confidence

A vulnerability in the Automated Logic and Carrier i-Vu Gen5 router driver (drv_gen5_106-01-2380) allows malformed BACnet MS/TP packets to be sent to affected devices, causing them to enter an unrecoverable fault state that requires manual power cycling to restore network visibility.

MitigationUpdate the driver to a patched version once available, implement network segmentation to restrict unauthorized BACnet MS/TP traffic, and monitor for malformed packets to detect exploitation attempts.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
Low
Privileges
None
Authentication
X
User interaction
None
Scope
X

CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:L/VA:L/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Identify if Automated Logic or Carrier i-Vu Gen5 system is deployed
    Review your building automation system inventory or consult with your building management system administrator to confirm the presence of Automated Logic or Carrier i-Vu Gen5 controllers or routers in your environment.
    Affected if The environment contains Automated Logic or Carrier i-Vu Gen5 controllers or routers.
  2. Locate and verify the drv_gen5 driver version
    Access the building automation system controller or management interface and navigate to the driver or firmware section. Look for the driver identified as drv_gen5_106-01-2380 or similar gen5 router driver. Record the installed version number for comparison.
    Affected if The drv_gen5 driver version matches or falls within the affected range (specifically version 106-01-2380 or earlier unpatched versions).
  3. Confirm BACnet MS/TP protocol is enabled
    Check the configuration settings of the Gen5 router or controller. Locate the BACnet MS/TP protocol settings and verify whether this protocol interface is active and operational.
    Affected if BACnet MS/TP is enabled and actively communicating on the network.
  4. Inspect devices for fault state conditions
    Access the system monitoring dashboard or device status interface. Review all Gen5 router and connected BACnet MS/TP devices for any entries showing unrecoverable fault states, unexpected offline status, or alerts indicating loss of network visibility requiring manual intervention.
    Affected if Any Gen5 router or BACnet MS/TP device displays an unrecoverable fault state or is unreachable on the network.
  5. Analyze network traffic for malformed BACnet MS/TP packets
    Use a network packet capture tool on the BACnet MS/TP segment to capture and inspect BACnet traffic. Look for malformed, truncated, or anomalous BACnet MS/TP packets that do not conform to standard BACnet protocol specifications.
    Affected if Malformed BACnet MS/TP packets are detected on the network segment.

A user is affected if they have the vulnerable drv_gen5 driver version with BACnet MS/TP enabled and either observe devices in fault state or detect malformed BACnet MS/TP packets on the network.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

From vendor data
Mitigation available No clean upgrade yet — mitigate in the meantime
Mitigation

Update the driver to a patched version once available, implement network segmentation to restrict unauthorized BACnet MS/TP traffic, and monitor for malformed packets to detect exploitation attempts.

Have this fixed Scoped from the published advisory
  • Consultation4.0 h
  • Implementation8.0 h
  • Testing6.0 h
  • Review / QA2.0 h
20.0 hours of engineering $3,500
Get help mitigating

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $5,600.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2025-0657 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2025-0657 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data