CVE-2025-13824
Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.
NVD · uneditedA security issue exists due to improper handling of malformed CIP packets during fuzzing. The controller enters a hard fault with solid red Fault LED and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF019. To recover, clear the fault.
Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.
dbcve analysis · moderate confidenceImproper handling of malformed CIP (Common Industrial Protocol) packets allows remote attackers to cause a denial-of-service condition on affected industrial controllers. The controller enters a hard fault state with solid red Fault LED, becomes unresponsive, and after power cycle enters a recoverable fault with specific LED patterns (0xF019 fault code) requiring manual fault clearing.
Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.
CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.
From the vector- Attack vector
- Network
- Complexity
- Low
- Privileges
- None
- Authentication
- X
- User interaction
- None
- Scope
- X
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.
dbcve checksWork through these to decide whether this CVE applies to you.
-
Identify CIP-enabled controllers in the environmentInventory all industrial controllers, programmable logic controllers (PLCs), and SCADA devices. Check device documentation or management interfaces for CIP (Common Industrial Protocol) or EtherNet/IP support. Look for Allen-Bradley, Schneider Electric, or other major industrial controller brands that commonly implement CIP.Affected if The environment contains any industrial controllers that support CIP protocol for communication.
-
Determine controller firmware versionAccess each CIP-enabled controller via its management interface, industrial protocol tools (such as RSLinx, Studio 5000, or vendor-specific utilities), or check the device firmware revision displayed on the controller's built-in web interface or programming software.Affected if The installed firmware version is older than any vendor-provided patch addressing this vulnerability, or if no patch has yet been released for that specific controller model.
-
Check network exposure of CIP portsScan the network for open ports commonly used by CIP/EtherNet/IP (port 44818/TCP is primary; port 2222/TCP may also be used). Identify which CIP-enabled controllers are reachable from network segments that are not behind industrial firewalls or VLANs dedicated to operational technology.Affected if CIP-enabled controllers are directly accessible from corporate networks, the internet, or other untrusted network segments without intermediate filtering.
-
Verify CIP packet filtering at network boundariesReview firewall rules, network segmentation policies, or intrusion detection/prevention systems (IDS/IPS) deployed between IT and OT networks. Confirm whether there are explicit rules to inspect, validate, or block malformed CIP packets before they reach controllers.Affected if No CIP-specific packet validation, deep packet inspection, or filtering is applied at network boundaries, and malformed packets could reach controllers unimpeded.
-
Inspect for existing fault conditionsCheck controller status indicators for solid red Fault LED, review controller event logs or fault history for fault code 0xF019, and verify whether operators have reported controllers entering unresponsive or hard fault states.Affected if Controllers are currently exhibiting hard fault states, displaying 0xF019 fault codes, or have required manual fault clearing after power cycles.
A user is affected if their environment contains CIP-enabled industrial controllers with vulnerable firmware versions that can receive malformed CIP packets from an accessible network segment lacking proper packet filtering.
Generated from the published advisory. Verify against your own configuration.
Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.
From vendor dataApply vendor-supplied firmware patches when available. In the interim, implement network segmentation and CIP packet filtering at the edge to block malformed packets from reaching affected controllers. Ensure operators are trained on the fault recovery procedure.
- Consultation4.0 h
- Implementation2.0 h
- Testing8.0 h
- Review / QA4.0 h
An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $4,928.
Scan for this in your stack
Free · runs locallyCheck whether your project pulls in CVE-2025-13824 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.
References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.
Primary sourcesPractitioner notes
ContributedPeer-ranked notes from engineers who’ve handled CVE-2025-13824 in production — separate from our analysis above.
The advisory tells you what broke. It rarely tells you what actually worked. If you’ve dealt with this one, that detail is what the next engineer is searching for.
- The version that genuinely resolved it — not the one the vendor claimed
- A config change or rule that shut the vector down
- A gotcha in the upgrade path that cost you an afternoon
No notes yet
Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.
A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.
- Verified mitigations, workarounds, and config changes
- Version or environment caveats, and links to real fixes
- No weaponised exploit code, or anything meant to cause harm