CVE-2025-1384

HIGH · 7.0 CVSS v3.1 Published 2025-07-14
Mitigation only
No fix yet — a mitigation exists. There is no fixed release. A documented workaround reduces exposure in the meantime.
See remediation →
79/100
Remediation priority · High
Remotely reachable No privileges Zero-click

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
Least Privilege Violation (CWE-272) Vulnerability exists in the communication function between the NJ/NX-series Machine Automation Controllers and the Sysmac Studio Software. An attacker may use this vulnerability to perform unauthorized access and to execute unauthorized code remotely to the controller products.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · moderate confidence

A least privilege violation exists in the communication function between Omron NJ/NX-series Machine Automation Controllers and Sysmac Studio engineering software. The vulnerability allows an attacker to bypass intended access controls in the controller communication protocol, enabling unauthorized access and potentially remote code execution on the affected controller devices.

MitigationApply vendor-supplied firmware updates to affected NJ/NX-series controllers and update Sysmac Studio to the latest version. Review network segmentation and access controls to limit exposure of controller communication interfaces until patches are applied.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
High
Privileges
None
User interaction
None
Scope
Unchanged
Confidentiality
Low
Integrity
Low
Availability
High

CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:L/A:H

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Identify Omron NJ/NX controllers on the network
    Review network documentation, scan for devices responding to Omron protocol ports (typically TCP/5080 for FINS, or check for Omron-specific device signatures), or query your asset inventory for NJ-series or NX-series Machine Automation Controllers
    Affected if Any NJ or NX-series controller is present in the environment and accessible on the network
  2. Determine Sysmac Studio installation and version
    On engineering workstations, check for installed Sysmac Studio software (typically in Program Files/Omron/Sysmac Studio or via Windows Programs and Features), right-click the application in the start menu and select Properties to view the version field
    Affected if Sysmac Studio is installed and the installed version falls within the affected version range (compare against vendor advisory)
  3. Verify controller communication is enabled
    Examine the NJ/NX controller configuration via Sysmac Studio by connecting to the controller, navigating to Controller Setup > Communications Setup, or checking if the controller has an active Ethernet/IP or FINS communication service configured and running
    Affected if Controller communication protocols (Ethernet/IP, FINS over Ethernet, or NJ/NX proprietary protocols) are enabled and the controller is networked
  4. Check network exposure of controller interfaces
    Review firewall rules, network segmentation, and access control lists to determine if the controller communication ports (TCP/5080, UDP/5080 for FINS, or Ethernet/IP ports 44818/2222) are exposed beyond the industrial network segment or accessible from less-trusted networks
    Affected if Controller communication interfaces are accessible from outside the dedicated industrial network segment or from unauthorized IP addresses
  5. Review controller user access configuration
    Connect to the NJ/NX controller via Sysmac Studio and inspect the Controller Security settings (Controller Setup > Security) to verify the configured user accounts, their privilege levels, and whether remote engineering access is permitted
    Affected if Remote engineering communication is enabled or any user accounts with elevated privileges are configured for network-based access

A user is affected if they have any Omron NJ or NX-series controllers with Sysmac Studio communication enabled and the installed version of either component falls within the affected range, particularly if the controller interface is accessible from the network.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

From vendor data
Mitigation available No clean upgrade yet — mitigate in the meantime
Mitigation

Apply vendor-supplied firmware updates to affected NJ/NX-series controllers and update Sysmac Studio to the latest version. Review network segmentation and access controls to limit exposure of controller communication interfaces until patches are applied.

Have this fixed Scoped from the published advisory
  • Consultation4.0 h
  • Implementation8.0 h
  • Testing12.0 h
  • Review / QA4.0 h
28.0 hours of engineering $4,760
Get help mitigating

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $7,616.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2025-1384 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2025-1384 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data