CWE-250Weakness · CWE-250

CVE-2025-13911

MEDIUM · 6.4 CVSS v3.1 Published 2025-12-18
Mitigation only
No fix yet — a mitigation exists. There is no fixed release. A documented workaround reduces exposure in the meantime.
See remediation →
66/100
Remediation priority · Elevated
Zero-click

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
Ignition by Inductive Automation, when installed with default OS service account settings, may expose the host system to an elevated code execution risk via the gateway backup restore functionality. An authenticated user with Gateway Administrator privileges can import a malicious gateway backup (.gwbk) file containing crafted project resources, scripts, or modules, resulting in code execution on the host system. This affects both Windows and Linux installations. On Windows, default installations often run the Ignition service as NT AUTHORITY\SYSTEM, resulting in code execution with full local system privileges. On Linux, default installations commonly run the Ignition service as root or with elevated privileges. Specific privilege level depends on installation configuration.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · moderate confidence

Ignition SCADA allows authenticated administrators to import arbitrary Python libraries through project files without restrictions. When combined with the Ignition Gateway running with SYSTEM-level permissions on Windows, a malicious project containing bind shell Python scripts can execute with elevated privileges, achieving code execution beyond the intended application context.

MitigationConfigure the Ignition Gateway service to run with a dedicated, least-privilege service account instead of SYSTEM, and implement Python module import restrictions or a sandboxing policy to prevent execution of unauthorized libraries.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Adjacent
Complexity
High
Privileges
High
User interaction
None
Scope
Unchanged
Confidentiality
High
Integrity
High
Availability
High

CVSS:3.1/AV:A/AC:H/PR:H/UI:N/S:U/C:H/I:H/A:H

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Verify Ignition SCADA installation and version
    Check for Ignition Gateway installation directory (typically C:\Program Files\Inductive Automation\Ignition) and locate the version info in about or gateway status pages
    Affected if Ignition SCADA is installed and running, but no specific version range is provided for comparison
  2. Confirm Windows service account configuration
    Open Windows Services, locate the 'Ignition Gateway' service, right-click and select Properties, then examine the 'Log On As' field
    Affected if The service is configured to run as 'Local System account' or 'SYSTEM' with elevated privileges
  3. Inspect Python module import restrictions
    Access Ignition Gateway Config > System > Gateway Settings, or check for python.policy files in the Ignition data directory for module import controls
    Affected if No Python module import restrictions, sandboxing policy, or allowlist is configured for project imports
  4. Review installed project files for unauthorized scripts
    Navigate to Ignition Gateway web UI > Config > Projects, examine imported project files, and check the 'lib' or 'python' subdirectories within projects for unexpected .py files
    Affected if Projects contain Python libraries or scripts that were not explicitly reviewed or that attempt to bind to network ports or execute system commands

You are affected if Ignition SCADA is running with Gateway service as SYSTEM on Windows and no Python module import restrictions or sandboxing policy are configured, allowing administrators to import and execute arbitrary Python code with elevated privileges.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

From vendor data
Mitigation available No clean upgrade yet — mitigate in the meantime
Mitigation

Configure the Ignition Gateway service to run with a dedicated, least-privilege service account instead of SYSTEM, and implement Python module import restrictions or a sandboxing policy to prevent execution of unauthorized libraries.

Have this fixed Scoped from the published advisory
  • Consultation6.0 h
  • Implementation12.0 h
  • Testing6.0 h
  • Review / QA3.0 h
27.0 hours of engineering $4,800
Get help mitigating

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $7,680.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2025-13911 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2025-13911 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data