Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
Insecure default settings have been found in recorder products provided by Yokogawa Electric Corporation. The default setting of the authentication function is disabled on the affected products. Therefore, when connected to a network with default settings, anyone can access all functions related to settings and operations. As a result, an attacker can illegally manipulate and configure important data such as measured values and settings. This issue affects GX10 / GX20 / GP10 / GP20 Paperless Recorders: R5.04.01 or earlier; GM Data Acquisition System: R5.05.01 or earlier; DX1000 / DX2000 / DX1000N Paperless Recorders: R4.21 or earlier; FX1000 Paperless Recorders: R1.31 or earlier; μR10000 / μR20000 Chart Recorders: R1.51 or earlier; MW100 Data Acquisition Units: All versions; DX1000T / DX2000T Paperless Recorders: All versions; CX1000 / CX2000 Paperless Recorders: All versions.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · high confidence

Insecure default settings in Yokogawa recorder products leave authentication disabled by default, allowing unauthenticated network attackers to access all settings and operational functions. The vulnerability affects multiple product lines across various firmware versions.

MitigationEnable authentication on affected devices before connecting to any network, and implement network segmentation to isolate industrial control devices from untrusted networks.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
Low
Privileges
None
User interaction
None
Scope
Unchanged
Confidentiality
High
Integrity
High
Availability
High

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Identify the device model and firmware version
    Access the device web interface or check the system information page. For Yokogawa recorders, navigate to Maintenance > System Information or look for a firmware version display on the main screen. Record the exact model number and firmware version.
    Affected if The device is a Yokogawa recorder and the firmware version falls within any affected version range for that product line.
  2. Verify if authentication is enabled
    Navigate to the device security or user management settings. Look for options such as 'Authentication', 'User Authentication', 'Login Authentication', or similar. Check if there is a setting to enable/disable authentication for web access or network access.
    Affected if Authentication is shown as disabled, or there is no login prompt when accessing the device web interface.
  3. Test for unauthenticated access
    Attempt to access the device web interface without providing any credentials. Try accessing common paths like the main page, settings pages, or data export functions without logging in.
    Affected if The device allows full access to settings, configuration, or operational functions without requiring any username or password.
  4. Check network exposure
    Examine the device network configuration. Look for IP address settings, subnet mask, and gateway configuration. Determine if the device is connected to a network that is accessible from untrusted networks.
    Affected if The device has an IP address on a network segment that is not isolated from untrusted networks, or is directly accessible via the internet.
  5. Review security settings for default accounts
    Check the user account configuration page. Look for default or factory-set accounts. Verify if there are any accounts with blank passwords or known default credentials.
    Affected if Default accounts exist with blank passwords or no authentication is required for any account.

The environment is affected if a Yokogawa recorder device has authentication disabled (the insecure default) and is accessible from a network where untrusted attackers could reach it.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

From vendor data
Mitigation available No clean upgrade yet — mitigate in the meantime
Mitigation

Enable authentication on affected devices before connecting to any network, and implement network segmentation to isolate industrial control devices from untrusted networks.

Have this fixed Scoped from the published advisory
  • Consultation4.0 h
  • Implementation8.0 h
  • Testing6.0 h
  • Review / QA2.0 h
20.0 hours of engineering $3,500
Get help mitigating

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $5,600.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2025-1863 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2025-1863 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data