CWE-327Weakness · CWE-327

CVE-2025-24007

HIGH · 7.5 CVSS v3.1 Published 2025-05-13
Mitigation only
No fix yet — a mitigation exists. There is no fixed release. A documented workaround reduces exposure in the meantime.
See remediation →
84/100
Remediation priority · High
Remotely reachable No privileges Zero-click

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
A vulnerability has been identified in SIRIUS 3RK3 Modular Safety System (MSS) (All versions), SIRIUS Safety Relays 3SK2 (All versions). Affected devices only provide weak password obfuscation. An attacker with network access could retrieve and de-obfuscate the safety password used for protection against inadvertent operating errors.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · high confidence

The SIRIUS 3RK3 MSS and 3SK2 Safety Relays use weak password obfuscation rather than proper cryptographic protection. An attacker with network access can intercept the obfuscated safety password and trivially de-obfuscate it, bypassing the protection against inadvertent operating errors. This is a fundamental flaw in how credentials are stored/transmitted.

MitigationRestrict network access to affected devices via firewalls or network segmentation; contact Siemens for formal patch/fix; implement compensating controls such as physical access restrictions until vendor solution is available.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
Low
Privileges
None
User interaction
None
Scope
Unchanged
Confidentiality
High
Integrity
None
Availability
None

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Identify SIRIUS safety relay devices
    Inventory your industrial network for Siemens 3RK3 MSS or 3SK2 Safety Relay devices. Check device nameplates, engineering software (e.g., SIRIUS Safety Matrix or TIA Portal), or network documentation for these model numbers.
    Affected if Either the 3RK3 MSS or 3SK2 Safety Relay is present in the environment
  2. Verify network connectivity is enabled
    Check device configuration settings for Ethernet, PROFINET, or other network interfaces. In the device web interface or engineering software, look for network communication parameters under communication or interface settings.
    Affected if Network communication (Ethernet, PROFINET, or similar) is enabled on the safety relay, allowing remote network access
  3. Confirm password protection uses obfuscation
    In the device configuration software or web interface, navigate to the safety password or access protection settings. Observe whether the password storage or transmission method appears to use simple obfuscation (Base64, encoding, or clear-text with minimal transformation) rather than cryptographic hashing or encryption.
    Affected if A safety password is configured and uses weak obfuscation rather than proper cryptographic protection for storage or transmission
  4. Monitor network traffic for password exposure
    Use a network sniffer or packet capture tool on the industrial network segment to capture traffic between the engineering station and the safety relay. Inspect captured packets for the safety password being transmitted in obfuscated form that can be trivially reversed.
    Affected if Network captures reveal the safety password in an easily reversible format traversing the network

Your environment is affected if you have 3RK3 MSS or 3SK2 Safety Relay devices with network connectivity enabled and a configured safety password using weak obfuscation rather than cryptographic protection.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

From vendor data
Mitigation available No clean upgrade yet — mitigate in the meantime
Mitigation

Restrict network access to affected devices via firewalls or network segmentation; contact Siemens for formal patch/fix; implement compensating controls such as physical access restrictions until vendor solution is available.

Have this fixed Scoped from the published advisory
  • Consultation8.0 h
  • Implementation16.0 h
  • Testing12.0 h
  • Review / QA8.0 h
44.0 hours of engineering $7,720
Get help mitigating

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $12,352.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2025-24007 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2025-24007 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data