CVE-2025-2523
Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.
NVD · uneditedThe Honeywell Experion PKS and OneWireless WDM contains an Integer Underflow vulnerability in the component Control Data Access (CDA). An attacker could potentially exploit this vulnerability, leading to a Communication Channel Manipulation, which could result in a failure during subtraction allowing remote code execution. Honeywell recommends updating to the most recent version of Honeywell Experion PKS:520.2 TCU9 HF1 and 530.1 TCU3 HF1 and OneWireless: 322.5 and 331.1. The affected Experion PKS products are C300 PCNT02, C300 PCNT05, FIM4, FIM8, UOC, CN100, HCA, C300PM, and C200E. The Experion PKS versions affected are from 520.1 through 520.2 TCU9 and from 530 through 530 TCU3. The OneWireless WDM affected versions are 322.1 through 322.4 and 330.1 through 330.3.
Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.
dbcve analysis · high confidenceInteger underflow vulnerability in Honeywell Experion PKS and OneWireless WDM's Control Data Access (CDA) component allows attackers to manipulate communication channels through a subtraction underflow condition, potentially achieving remote code execution.
Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.
CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.
From the vector- Attack vector
- Network
- Complexity
- Low
- Privileges
- None
- User interaction
- None
- Scope
- Unchanged
- Confidentiality
- Low
- Integrity
- High
- Availability
- High
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:H/A:H
Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.
dbcve checksWork through these to decide whether this CVE applies to you.
-
Identify installed Honeywell productCheck system inventory or running services for Experion PKS or OneWireless WDM installations. Look for CDA (Control Data Access) service or process.Affected if Neither Experion PKS nor OneWireless WDM is present, the system is not affected.
-
Determine Experion PKS versionLocate the Experion installation directory and check version files, or use the Honeywell deployment/console tool to query the installed TCU (Total Control Upgrade) version.Affected if Version is earlier than 520.2 TCU9 or 530.1 TCU3, or cannot be determined and the product is Experion PKS.
-
Determine OneWireless WDM versionCheck the Wireless Device Manager installation for its version identifier, typically found in the WDM configuration or deployment metadata.Affected if Version is earlier than 322.5 or 331.1, or cannot be determined and the product is OneWireless WDM.
-
Verify CDA component statusCheck if the Control Data Access component is running or enabled in the Honeywell system configuration. Look for CDA services, modules, or network listeners.Affected if CDA component is enabled and exposed on the network, and version is in the affected range.
A system is affected if it runs Experion PKS versions before 520.2 TCU9/530.1 TCU3 or OneWireless WDM versions before 322.5/331.1, with the CDA component enabled and accessible.
Generated from the published advisory. Verify against your own configuration.
Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.
dbcve · scopedUpdate Experion PKS to versions 520.2 TCU9 HF1 or 530.1 TCU3 HF1, and OneWireless WDM to versions 322.5 or 331.1 as recommended by Honeywell.
Honeywell Experion PKS: 520.2 TCU9 HF1 or 530.1 TCU3 HF1; OneWireless WDM: 322.5 or 331.1
- 1. Identify the current version of Honeywell Experion PKS or OneWireless WDM by accessing the system management interface or using the version check utility.
- 2. Confirm the system is running an affected version: Experion PKS 520.1 through 520.2 TCU9 or 530 through 530 TCU3; OneWireless WDM 322.1 through 322.4 or 330.1 through 330.3.
- 3. Create a full backup of the system configuration and ensure a restore point is available in case of upgrade issues.
- 4. Download the recommended fixed version from the Honeywell process.honeywell.com portal or official distribution channels: Experion PKS 520.2 TCU9 HF1 or 530.1 TCU3 HF1; OneWireless 322.5 or 331.1.
- 5. Apply the upgrade following the Honeywell deployment and installation documentation specific to your hardware model (C300 PCNT02, C300 PCNT05, FIM4, FIM8, UOC, CN100, HCA, C300PM, or C200E for Experion PKS).
- 6. After upgrade completion, verify the CDA component is running the patched version by checking the system information or release notes.
- 7. Test critical control functions and validate that the integer underflow vulnerability is remediated and normal operations are restored.
Generated from the published advisory — verify against the referenced sources before acting.
- Consultation8.0 h
- Implementation12.0 h
- Testing16.0 h
- Review / QA8.0 h
An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $12,160.
Scan for this in your stack
Free · runs locallyCheck whether your project pulls in CVE-2025-2523 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.
References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.
Primary sourcesPractitioner notes
ContributedPeer-ranked notes from engineers who’ve handled CVE-2025-2523 in production — separate from our analysis above.
The advisory tells you what broke. It rarely tells you what actually worked. If you’ve dealt with this one, that detail is what the next engineer is searching for.
- The version that genuinely resolved it — not the one the vendor claimed
- A config change or rule that shut the vector down
- A gotcha in the upgrade path that cost you an afternoon
No notes yet
Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.
A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.
- Verified mitigations, workarounds, and config changes
- Version or environment caveats, and links to real fixes
- No weaponised exploit code, or anything meant to cause harm