CVE-2025-27257
Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.
NVD · uneditedInsufficient Verification of Data Authenticity vulnerability in GE Vernova UR IED family devices allows an authenticated user to install a modified firmware. The firmware signature verification is enforced only on the client-side dedicated software Enervista UR Setup, allowing the integration check to be bypassed.
Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.
dbcve analysis · high confidenceThe GE Vernova UR IED devices have a vulnerability where firmware signature verification is only performed client-side by the Enervista UR Setup software. The actual IED device does not verify the authenticity of firmware before installation, allowing an authenticated attacker to install modified (potentially malicious) firmware by bypassing the client-side integrity check.
Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.
CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.
From the vector- Attack vector
- Adjacent
- Complexity
- Low
- Privileges
- High
- User interaction
- None
- Scope
- Unchanged
- Confidentiality
- None
- Integrity
- High
- Availability
- High
CVSS:3.1/AV:A/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:H
Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.
dbcve checksWork through these to decide whether this CVE applies to you.
-
Identify the device modelCheck the device nameplate, web interface, or SNMP inventory to confirm the device is a GE Vernova UR series IED (Intelligent Electronic Device)Affected if The device is a GE Vernova UR IED model and firmware updates are performed via Enervista UR Setup software
-
Verify firmware update accessCheck network access controls, user accounts, and physical security to determine if an authenticated user could access the Enervista UR Setup software firmware update functionAffected if Unrestricted or inadequately controlled access exists to the firmware update capability through Enervista UR Setup software
-
Check network exposureReview firewall rules, VLAN placement, and access control lists to determine if the IED device management interface is accessible from less-trusted network segmentsAffected if The device management interface (used by Enervista UR Setup) is reachable from networks accessible to untrusted users
-
Audit existing firmware uploadsReview system logs, audit trails, or change management records for any firmware installation events on the IED deviceAffected if Firmware updates have been performed and cannot be verified as originating from vendor-signed packages
-
Verify Enervista software versionCheck the installed version of Enervista UR Setup software against vendor release notes to confirm client-side signature validation is present in your versionAffected if The Enervista UR Setup version does not include device-side firmware signature verification enforcement
The environment is affected if a GE Vernova UR IED device uses Enervista UR Setup for firmware updates and the device or its management software is accessible to authenticated attackers who could supply modified firmware packages.
Generated from the published advisory. Verify against your own configuration.
Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.
From vendor dataApply vendor-provided firmware updates when available. In the interim, restrict access to the Enervista UR Setup software and firmware update functions to only necessary personnel, and implement network segmentation and monitoring to detect unauthorized firmware changes.
- Consultation8.0 h
- Implementation16.0 h
- Testing12.0 h
- Review / QA8.0 h
An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $12,352.
Scan for this in your stack
Free · runs locallyCheck whether your project pulls in CVE-2025-27257 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.
References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.
Primary sourcesPractitioner notes
ContributedPeer-ranked notes from engineers who’ve handled CVE-2025-27257 in production — separate from our analysis above.
The advisory tells you what broke. It rarely tells you what actually worked. If you’ve dealt with this one, that detail is what the next engineer is searching for.
- The version that genuinely resolved it — not the one the vendor claimed
- A config change or rule that shut the vector down
- A gotcha in the upgrade path that cost you an afternoon
No notes yet
Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.
A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.
- Verified mitigations, workarounds, and config changes
- Version or environment caveats, and links to real fixes
- No weaponised exploit code, or anything meant to cause harm
- No spam, self-promotion, credentials, or personal data