Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
Improper Validation of Specified Index, Position, or Offset in Input vulnerability in Mitsubishi Electric Corporation MELSEC iQ-F Series CPU modules allows a remote unauthenticated attacker to read information in the product, to cause a Denial-of-Service (DoS) condition in MELSOFT connection, or to stop the operation of the CPU module (causing a DoS condtion on the CPU module), by sending specially crafted packets. The product is needed to reset for recovery.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · high confidence

Improper validation of specified index, position, or offset in input in Mitsubishi Electric MELSEC iQ-F Series CPU modules allows remote unauthenticated attackers to send specially crafted packets to read sensitive information, cause DoS in MELSOFT connections, or stop CPU module operation, requiring a product reset for recovery.

MitigationApply vendor firmware updates when available; restrict network access to PLC devices using firewalls/VLANs; monitor for anomalous MELSOFT connection activity; implement compensating controls such as network segmentation for operational technology assets.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
Low
Privileges
None
User interaction
None
Scope
Unchanged
Confidentiality
High
Integrity
None
Availability
High

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:H

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Identify the MELSEC iQ-F Series CPU module
    Access the CPU module via engineering software (GX Works3) or check the physical device labeling. Confirm the model number matches the MELSEC iQ-F Series product line (e.g., FX5U, FX5UC, FX5UJ CPU modules).
    Affected if The device is a MELSEC iQ-F Series CPU module.
  2. Verify MELSOFT connection configuration
    In GX Works3, go to the CPU module parameters and check MELSOFT connection settings under Ethernet port configuration. Confirm whether MELSOFT connection (TCP/UDP port 5000-5007) is enabled.
    Affected if MELSOFT connections are enabled and the device is accessible over the network.
  3. Check firmware version
    In GX Works3, connect to the CPU module and navigate to System Information or CPU Module Diagnostics. Record the firmware version displayed. Compare this version to any vendor-released firmware updates for CVE-2025-3755.
    Affected if The installed firmware version is older than the version that addresses this vulnerability (once released by Mitsubishi Electric).
  4. Inspect for unexpected CPU resets
    In GX Works3, review the CPU module event log or history for frequent resets, error codes, or sudden stop conditions. Check the Alarm History for entries indicating CPU stop or unexpected operation中断.
    Affected if The CPU module has experienced unexplained resets, frequent errors, or operation stops that coincide with network activity.
  5. Monitor network traffic for anomalous MELSOFT patterns
    Use a network sniffer or IDS to capture traffic on ports 5000-5007 (MELSOFT ports). Look for unusually high volumes of packets, malformed packets, or connections from unauthorized IP addresses.
    Affected if Unusual or malformed MELSOFT traffic is detected, or connections originate from untrusted sources.

Your environment is affected if you have a MELSEC iQ-F Series CPU module with MELSOFT connections enabled and your firmware version predates the vendor patch for this input validation vulnerability.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

From vendor data
Mitigation available No clean upgrade yet — mitigate in the meantime
Mitigation

Apply vendor firmware updates when available; restrict network access to PLC devices using firewalls/VLANs; monitor for anomalous MELSOFT connection activity; implement compensating controls such as network segmentation for operational technology assets.

Have this fixed Scoped from the published advisory
  • Consultation8.0 h
  • Implementation16.0 h
  • Testing12.0 h
  • Review / QA8.0 h
44.0 hours of engineering $7,720
Get help mitigating

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $12,352.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2025-3755 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2025-3755 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data