CVE-2025-3756
Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.
NVD · uneditedA vulnerability exists in the command handling of the IEC 61850 communication stack included in the product revisions listed as affected in this CVE. An attacker with access to IEC 61850 networks could exploit the vulnera bility by using a specially crafted 61850 packet, forcing the communication interfaces of the PM 877, CI850 and CI868 modules into fault mode or causing unavailability of the S+ Operations 61850 connectivity, resulting in a denial-of-service situation. The System 800xA IEC61850 Connect is not affected. Note: This vulnerability does not impact on the overall availability and functionality of the S+ Operations node, only the 61850 communication function. This issue affects AC800M (System 800xA): from 6.0.0x through 6.0.0303.0, from 6.1.0x through 6.1.0031.0, from 6.1.1x through 6.1.1004.0, from 6.1.1x through 6.1.1202.0, from 6.2.0x through 6.2.0006.0; Symphony Plus SD Series: A_0, A_1, A_2.003, A_3.005, A_4.001, B_0.005; Symphony Plus MR (Melody Rack): from 3.10 through 3.52; S+ Operations: 2.1, 2.2, 2.3, 3.3.
Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.
dbcve analysis · high confidenceA command handling vulnerability in the IEC 61850 communication stack allows an attacker with network access to send specially crafted 61850 packets, forcing the PM 877, CI850, and CI868 module communication interfaces into fault mode and causing denial of the S+ Operations 61850 connectivity function. The vulnerability does not affect the overall S+ Operations node availability.
Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.
CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.
From the vector- Attack vector
- Adjacent
- Complexity
- Low
- Privileges
- None
- User interaction
- None
- Scope
- Unchanged
- Confidentiality
- None
- Integrity
- None
- Availability
- High
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.
dbcve checksWork through these to decide whether this CVE applies to you.
-
Identify installed hardware modulesReview system inventory or hardware configuration to determine if PM 877, CI850, or CI868 communication modules are present in the S+ Operations environmentAffected if Any of these three modules (PM 877, CI850, CI868) are installed
-
Verify IEC 61850 protocol stack is enabledCheck the S+ Operations configuration settings for IEC 61850 protocol stack activation statusAffected if IEC 61850 protocol stack is enabled in the system configuration
-
Confirm S+ Operations 61850 connectivity function statusCheck the status of the S+ Operations 61850 connectivity function through the system management interface or logsAffected if S+ Operations 61850 connectivity function is active and running
-
Assess network exposure of IEC 61850 interfacesReview network configuration to determine if IEC 61850 ports are accessible from untrusted networksAffected if IEC 61850 interfaces are network-accessible beyond trusted segments
The environment is affected if PM 877, CI850, or CI868 modules are present with IEC 61850 connectivity enabled and accessible over the network.
Generated from the published advisory. Verify against your own configuration.
Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.
dbcve · scopedApply vendor-provided patches to affected product revisions; implement network segmentation to restrict IEC 61850 network access to authorized devices only.
Contact ABB for specific fixed versions beyond affected ranges (6.2.0+ for AC800M, newer than B_0.005 for SD Series, newer than 3.52 for MR, newer than 3.3 for S+ Operations)
- 1. Identify the specific product and version currently deployed from the affected list (AC800M, Symphony Plus SD Series, Symphony Plus MR, or S+ Operations)
- 2. Contact ABB Technical Support to obtain the specific fixed version or patch for your product and version
- 3. Request ABB security advisory or patch specifically addressing CVE-2025-3756 for the IEC 61850 communication stack
- 4. Plan maintenance window for applying the fix
- 5. Before applying, backup current configuration
- 6. Apply the ABB-provided fix (patch or upgrade)
- 7. Verify IEC 61850 communication functions are operational after fix
Generated from the published advisory — verify against the referenced sources before acting.
- Consultation8.0 h
- Implementation16.0 h
- Testing12.0 h
- Review / QA6.0 h
An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $11,776.
Scan for this in your stack
Free · runs locallyCheck whether your project pulls in CVE-2025-3756 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.
References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.
Primary sourcesPractitioner notes
ContributedPeer-ranked notes from engineers who’ve handled CVE-2025-3756 in production — separate from our analysis above.
The advisory tells you what broke. It rarely tells you what actually worked. If you’ve dealt with this one, that detail is what the next engineer is searching for.
- The version that genuinely resolved it — not the one the vendor claimed
- A config change or rule that shut the vector down
- A gotcha in the upgrade path that cost you an afternoon
No notes yet
Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.
A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.
- Verified mitigations, workarounds, and config changes
- Version or environment caveats, and links to real fixes
- No weaponised exploit code, or anything meant to cause harm
- No spam, self-promotion, credentials, or personal data