CVE-2025-3946
Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.
NVD · uneditedThe Honeywell Experion PKS and OneWireless WDM contains a Deployment of Wrong Handler vulnerability in the component Control Data Access (CDA). An attacker could potentially exploit this vulnerability, leading to Input Data Manipulation, which could result in incorrect handling of packets leading to remote code execution. Honeywell recommends updating to the most recent version of Honeywell Experion PKS:520.2 TCU9 HF1 and 530.1 TCU3 HF1 and OneWireless: 322.5 and 331.1. The affected Experion PKS products are C300 PCNT02, C300 PCNT05, FIM4, FIM8, UOC, CN100, HCA, C300PM, and C200E. The Experion PKS versions affected are from 520.1 through 520.2 TCU9 and from 530 through 530 TCU3. The OneWireless WDM affected versions are 322.1 through 322.4 and 330.1 through 330.3.
Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.
dbcve analysis · high confidenceThe vulnerability is a Deployment of Wrong Handler in the Control Data Access (CDA) component of Honeywell Experion PKS and OneWireless WDM industrial control systems. This incorrect handler processes packets improperly, allowing input data manipulation that can lead to remote code execution. The issue affects multiple C300 controller models, FIM modules, and wireless distribution management components in versions 520.1-520.2 TCU9, 530-530 TCU3 for Experion PKS, and 322.1-322.4, 330.1-330.3 for OneWireless.
Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.
CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.
From the vector- Attack vector
- Network
- Complexity
- Low
- Privileges
- None
- User interaction
- None
- Scope
- Unchanged
- Confidentiality
- None
- Integrity
- Low
- Availability
- High
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:H
Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.
dbcve checksWork through these to decide whether this CVE applies to you.
-
Identify Experion PKS or OneWireless deploymentInventory the ICS environment to determine if Honeywell Experion PKS or OneWireless WDM systems are present. Check network documentation, asset inventories, or physically inspect control system hardware for Honeywell labels.Affected if Either Honeywell Experion PKS or OneWireless WDM is deployed in the environment
-
Identify C300 controller modelsExamine the control system hardware for C300 controller modules. Check the controller physical labels, or query the system via the Experion configuration tools (such as Experion Builder or Station) for controller model information.Affected if C300 controller models are present in the system
-
Check Experion PKS versionUsing Experion Station or the System Controller interface, navigate to the system information or version display to retrieve the TCU version. Look for versions labeled as 520.1, 520.2 TCU9, 530, or 530 TCU3.Affected if The installed Experion PKS version falls within 520.1-520.2 TCU9 or 530-530 TCU3
-
Check OneWireless WDM versionAccess the OneWireless Network Manager or WDM configuration console. Retrieve the software version information, typically found in the About or System Information section.Affected if The installed OneWireless version falls within 322.1-322.4 or 330.1-330.3
-
Verify CDA component configurationCheck if the Control Data Access (CDA) component is enabled in the system. This can be done through the Experion configuration tools by examining the CDA service settings, or by reviewing the system architecture documentation for CDA module presence.Affected if The CDA component is present and configured in the system
The environment is affected if it runs Experion PKS versions 520.1-520.2 TCU9 or 530-530 TCU3, or OneWireless versions 322.1-322.4 or 330.1-330.3, with C300 controllers and an active CDA component.
Generated from the published advisory. Verify against your own configuration.
Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.
dbcve · scopedApply the vendor-recommended updates: Experion PKS 520.2 TCU9 HF1 or 530.1 TCU3 HF1, and OneWireless 322.5 or 331.1. Coordinate updates through proper change management for production ICS environments.
Experion PKS: 520.2 TCU9 HF1 or 530.1 TCU3 HF1; OneWireless WDM: 322.5 or 331.1
- 1. Identify the current version of the affected Honeywell Experion PKS CDA component (C300 PCNT02, C300 PCNT05, FIM4, FIM8, UOC, CN100, HCA, C300PM, or C200E) or OneWireless WDM device
- 2. For Experion PKS: If running version 520.1 through 520.2 TCU9, upgrade to 520.2 TCU9 HF1; if running version 530 through 530 TCU3, upgrade to 530.1 TCU3 HF1
- 3. For OneWireless WDM: If running version 322.1 through 322.4, upgrade to 322.5; if running version 330.1 through 330.3, upgrade to 331.1
- 4. Follow Honeywell's official upgrade procedures and documentation for the specific hardware model
- 5. After upgrade, verify the CDA component is running the patched version and confirm normal operation
Generated from the published advisory — verify against the referenced sources before acting.
- Consultation6.0 h
- Implementation8.0 h
- Testing12.0 h
- Review / QA4.0 h
An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $8,256.
Scan for this in your stack
Free · runs locallyCheck whether your project pulls in CVE-2025-3946 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.
References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.
Primary sourcesPractitioner notes
ContributedPeer-ranked notes from engineers who’ve handled CVE-2025-3946 in production — separate from our analysis above.
The advisory tells you what broke. It rarely tells you what actually worked. If you’ve dealt with this one, that detail is what the next engineer is searching for.
- The version that genuinely resolved it — not the one the vendor claimed
- A config change or rule that shut the vector down
- A gotcha in the upgrade path that cost you an afternoon
No notes yet
Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.
A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.
- Verified mitigations, workarounds, and config changes
- Version or environment caveats, and links to real fixes
- No weaponised exploit code, or anything meant to cause harm
- No spam, self-promotion, credentials, or personal data