CWE-191Weakness · CWE-191

CVE-2025-3947

HIGH · 8.2 CVSS v3.1 Published 2025-07-10
Mitigation only
No fix yet — a mitigation exists. There is no fixed release. A documented workaround reduces exposure in the meantime.
See remediation →
91/100
Remediation priority · Urgent
Remotely reachable No privileges Zero-click

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
The Honeywell Experion PKS contains an Integer Underflow vulnerability in the component Control Data Access (CDA). An attacker could potentially exploit this vulnerability, leading to Input Data Manipulation, which could result in improper integer data value checking during subtraction leading to a denial of service. Honeywell recommends updating to the most recent version of Honeywell Experion PKS:520.2 TCU9 HF1 and 530.1 TCU3 HF1. The affected Experion PKS products are C300 PCNT02, C300 PCNT05, FIM4, FIM8, UOC, CN100, HCA, C300PM, and C200E. The Experion PKS versions affected are from 520.1 through 520.2 TCU9 and from 530 through 530 TCU3.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · high confidence

Integer underflow vulnerability in Honeywell Experion PKS Control Data Access (CDA) component allows improper integer data value checking during subtraction operations, leading to denial of service via input data manipulation.

MitigationApply Honeywell's recommended updates: upgrade to Experion PKS 520.2 TCU9 HF1 or 530.1 TCU3 HF1 depending on the major version branch in use.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
Low
Privileges
None
User interaction
None
Scope
Unchanged
Confidentiality
None
Integrity
Low
Availability
High

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:H

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Confirm Experion PKS installation
    Check for Honeywell Experion PKS installation by looking for the installation directory (typically C:\Honeywell\Experion or /opt/honeywell/experion), or look for the 'Experion' or 'CDA' service running on the system via services.msc or systemctl
    Affected if Experion PKS is not installed or the CDA component is not present on the system, the vulnerability does not apply
  2. Identify CDA component version
    Locate the Control Data Access (CDA) component within the Experion installation - check file properties of cda.exe or related DLLs, or use Experion's built-in version information utility if available
    Affected if Unable to determine CDA version means the component may not be present or accessible for inspection
  3. Compare Experion PKS major version branch
    Identify whether the installation is on the 520.x or 530.x branch by checking the base Experion PKS version number in the installation
    Affected if The system is running Experion PKS 520.x or 530.x branch and the CDA component is in use
  4. Check for unpatched TCU level
    Check the TCU (Technical Cascade Update) level of the Experion installation - examine the full version string (e.g., 520.2, 530.1) and TCU number via the Experion system information panel or registry keys under HKLM\Software\Honeywell\Experion
    Affected if Running Experion PKS 520.x versions before TCU9, or 530.x versions before TCU3, indicates the CDA integer underflow patch has not been applied
  5. Verify CDA service accessibility
    Confirm the CDA component service is running and accessible - check if the CDA service is active in the Experion control environment and if network access or data input interfaces to CDA are exposed
    Affected if The CDA component is running and processing external or manipulated input data values

The environment is affected if Honeywell Experion PKS with the CDA component is installed and running a version in the 520.x branch before TCU9 or in the 530.x branch before TCU3.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

dbcve · scoped
Mitigation available No clean upgrade yet — mitigate in the meantime
Mitigation

Apply Honeywell's recommended updates: upgrade to Experion PKS 520.2 TCU9 HF1 or 530.1 TCU3 HF1 depending on the major version branch in use.

Recommended fix High confidence

520.2 TCU9 HF1 (for 520.x versions) or 530.1 TCU3 HF1 (for 530.x versions)

  1. Identify the current Experion PKS version and TCU (Trusted Copy Update) level
  2. Contact Honeywell Technical Support or your authorized Honeywell distributor to obtain the update package
  3. For systems currently on 520.x versions: upgrade to Experion PKS 520.2 TCU9 HF1
  4. For systems currently on 530.x versions: upgrade to Experion PKS 530.1 TCU3 HF1
  5. Follow Honeywell's standard procedures for applying Trusted Copy Updates (TCU)
  6. After upgrade, verify the CDA component is functioning correctly and the vulnerability is resolved
Caveat Industrial control system upgrades may require downtime windows and should be tested in a non-production environment before deployment; coordinate with plant operations

Generated from the published advisory — verify against the referenced sources before acting.

Have this fixed Scoped from the published advisory
  • Consultation8.0 h
  • Implementation12.0 h
  • Testing8.0 h
  • Review / QA4.0 h
32.0 hours of engineering $5,680
Get help mitigating

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $9,088.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2025-3947 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2025-3947 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data