Missing AuthenticationWeakness · CWE-306

CVE-2025-41703

HIGH · 7.5 CVSS v3.1 Published 2025-10-14
Mitigation only
No fix yet — a mitigation exists. There is no fixed release. A documented workaround reduces exposure in the meantime.
See remediation →
84/100
Remediation priority · High
Remotely reachable No privileges Zero-click

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
An unauthenticated remote attacker can cause a Denial of Service by turning off the output of the UPS via Modbus command.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · moderate confidence

An unauthenticated remote attacker can send Modbus commands to a UPS (Uninterruptible Power Supply) system to turn off its output, causing a denial of service. The vulnerability stems from a lack of authentication requirements for critical Modbus commands that control UPS functionality.

MitigationImplement authentication and authorization controls for Modbus commands, especially those affecting power output. Apply network segmentation to isolate UPS management interfaces from untrusted networks, and monitor for unauthorized Modbus command traffic.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
Low
Privileges
None
User interaction
None
Scope
Unchanged
Confidentiality
None
Integrity
None
Availability
High

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Identify UPS devices with Modbus interfaces
    Inventory network-connected UPS systems and identify which ones expose Modbus communication (typically TCP port 502). Consult UPS vendor documentation or scan the network for devices responding on Modbus ports.
    Affected if The organization operates UPS devices that support Modbus communication.
  2. Verify Modbus interface network exposure
    Determine whether the Modbus interface is accessible from network segments outside the trusted management network. Review firewall rules, ACLs, and network boundary configurations that control access to the UPS Modbus port.
    Affected if The Modbus interface is reachable from untrusted or external networks without filtering.
  3. Check if authentication is required for Modbus commands
    Consult the UPS device documentation and configuration settings to determine whether authentication, authorization, or access control lists are enforced for Modbus commands that control power output (e.g., output shutdown commands). Attempt to send a read-only Modbus command without credentials to test basic access controls.
    Affected if The UPS accepts Modbus commands without requiring authentication or authorization.
  4. Assess network segmentation of UPS management
    Verify whether UPS management interfaces, including Modbus, are isolated on a dedicated management VLAN or network segment separate from general production and user-accessible networks.
    Affected if UPS Modbus interfaces are on the same network segment as untrusted systems without logical or physical isolation.

A user is affected if their environment contains UPS devices with Modbus interfaces that are accessible from untrusted networks without authentication or network segmentation controls in place.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

From vendor data
Mitigation available No clean upgrade yet — mitigate in the meantime
Mitigation

Implement authentication and authorization controls for Modbus commands, especially those affecting power output. Apply network segmentation to isolate UPS management interfaces from untrusted networks, and monitor for unauthorized Modbus command traffic.

Have this fixed Scoped from the published advisory
  • Consultation6.0 h
  • Implementation12.0 h
  • Testing8.0 h
  • Review / QA4.0 h
30.0 hours of engineering $5,280
Get help mitigating

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $8,448.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2025-41703 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2025-41703 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data