CVE-2025-5022

MEDIUM · 6.5 CVSS v3.1 Published 2025-07-10
Mitigation only
No fix yet — a mitigation exists. There is no fixed release. A documented workaround reduces exposure in the meantime.
See remediation →
70/100
Remediation priority · Elevated
No privileges Zero-click

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
Weak Password Requirements vulnerability in Mitsubishi Electric Corporation photovoltaic system monitor “EcoGuideTAB” PV-DR004J all versions and PV-DR004JA all versions allows an attacker within the Wi-Fi communication range between the units of the product (measurement unit and display unit) to derive the password from the SSID. In addition, if the product is configured to enable the individual air conditioner control function, an attacker who has access to the Wi-Fi communication between the units by exploiting this vulnerability may be able to execute ECHONET Lite commands to perform operations such as turning the air conditioner on or off and changing the set temperature. The individual air conditioner control function is available only in display unit version 02.00.01 or later and measurement unit version 02.03.01 or later. The affected products discontinued in 2015, support ended in 2020.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · high confidence

The EcoGuideTAB photovoltaic monitor uses a weak password generation mechanism where the Wi-Fi password is derived from the SSID. An attacker within Wi-Fi range can capture the SSID and mathematically derive the password. If the optional air conditioner control function is enabled (display unit v02.00.01+ and measurement unit v02.03.01+), the attacker can also send ECHONET Lite commands to control HVAC functions.

MitigationThis discontinued product (EOL 2015, support ended 2020) has no vendor patch available. Recommended mitigations include: (1) decommission and replace the device with a supported product, (2) if continued use is required, disable the air conditioner control function and isolate the device on a dedicated network segment VLAN away from critical systems.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Adjacent
Complexity
Low
Privileges
None
User interaction
None
Scope
Unchanged
Confidentiality
High
Integrity
None
Availability
None

CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Identify EcoGuideTAB device
    Locate the photovoltaic monitor device on the network or physically inspect for EcoGuideTAB labeling
    Affected if The device is an EcoGuideTAB photovoltaic monitor
  2. Check display unit firmware version
    Access the device's admin interface or check the firmware version displayed on the display unit screen
    Affected if Display unit firmware is version 02.00.01 or higher
  3. Check measurement unit firmware version
    Access the device's admin interface or check the firmware version displayed on the measurement unit
    Affected if Measurement unit firmware is version 02.03.01 or higher
  4. Verify air conditioner control function status
    Access the device settings menu and check if the optional air conditioner control function is enabled
    Affected if Air conditioner control function is enabled (requires both display unit v02.00.01+ AND measurement unit v02.03.01+)

You are affected if you have an EcoGuideTAB device with display unit v02.00.01+ and measurement unit v02.03.01+ with the air conditioner control function enabled, making Wi-Fi password derivation and HVAC control possible for nearby attackers

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

From vendor data
Mitigation available No clean upgrade yet — mitigate in the meantime
Mitigation

This discontinued product (EOL 2015, support ended 2020) has no vendor patch available. Recommended mitigations include: (1) decommission and replace the device with a supported product, (2) if continued use is required, disable the air conditioner control function and isolate the device on a dedicated network segment VLAN away from critical systems.

Have this fixed Scoped from the published advisory
  • Consultation4.0 h
  • Implementation8.0 h
  • Testing4.0 h
  • Review / QA2.0 h
18.0 hours of engineering $3,200
Get help mitigating

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $5,120.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2025-5022 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2025-5022 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data