CVE-2025-7353
Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.
NVD · uneditedA security issue exists due to the web-based debugger agent enabled on Rockwell Automation ControlLogix® Ethernet Modules. If a specific IP address is used to connect to the WDB agent, it can allow remote attackers to perform memory dumps, modify memory, and control execution flow.
Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.
dbcve analysis · high confidenceRockwell Automation ControlLogix® Ethernet Modules have a web-based debugger agent (WDB) enabled by default. Attackers with knowledge of a specific IP address can connect to this exposed debugger to perform memory dumps, modify memory contents, and control execution flow, effectively allowing remote code execution on the industrial controller.
Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.
CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.
From the vector- Attack vector
- Network
- Complexity
- Low
- Privileges
- None
- Authentication
- X
- User interaction
- None
- Scope
- X
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.
dbcve checksWork through these to decide whether this CVE applies to you.
-
Identify ControlLogix Ethernet Module in useReview network inventory, asset management records, or physically inspect the industrial controller rack to confirm the presence of a ControlLogix Ethernet module (e.g., 1756-ENBT, 1756-EN2T, or similar series).Affected if A ControlLogix Ethernet module from the affected product family is deployed in the environment.
-
Check if WDB debugger is enabledAccess the web interface of the ControlLogix Ethernet module via its IP address and navigate to the diagnostics or advanced settings area to verify whether the WDB debugger agent is in an enabled state. Alternatively, consult the module configuration through Rockwell Studio 5000 or RSLinx to inspect debugger settings.Affected if The WDB debugger agent is shown as enabled or active in the module configuration.
-
Verify debugger network exposurePerform a port scan or banner grab against the IP address of the ControlLogix Ethernet module to identify open ports associated with the WDB debugger service. Check if the debugger interface responds to network requests from non-local hosts.Affected if The debugger service is listening on a reachable network port and accepts connections from remote hosts.
-
Review network access controlsExamine firewall rules, ACLs, VLAN configurations, and DMZ settings to determine whether the module IP address or debugger port is accessible from untrusted network segments, office networks, or external networks.Affected if No firewall or network segmentation blocks external or untrusted access to the debugger interface.
If a ControlLogix Ethernet module is present, the WDB debugger is enabled, and the debugger interface is network-accessible from untrusted sources, the environment is affected by CVE-2025-7353.
Generated from the published advisory. Verify against your own configuration.
Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.
From vendor dataImmediately disable or restrict access to the WDB debugger agent on affected ControlLogix Ethernet modules. Implement network segmentation and firewall rules to prevent unauthorized access to the debugger interface, and consult Rockwell Automation for official patches or hardened configurations.
- Consultation6.0 h
- Implementation8.0 h
- Testing6.0 h
- Review / QA3.0 h
An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $6,528.
Scan for this in your stack
Free · runs locallyCheck whether your project pulls in CVE-2025-7353 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.
References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.
Primary sourcesPractitioner notes
ContributedPeer-ranked notes from engineers who’ve handled CVE-2025-7353 in production — separate from our analysis above.
The advisory tells you what broke. It rarely tells you what actually worked. If you’ve dealt with this one, that detail is what the next engineer is searching for.
- The version that genuinely resolved it — not the one the vendor claimed
- A config change or rule that shut the vector down
- A gotcha in the upgrade path that cost you an afternoon
No notes yet
Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.
A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.
- Verified mitigations, workarounds, and config changes
- Version or environment caveats, and links to real fixes
- No weaponised exploit code, or anything meant to cause harm
- No spam, self-promotion, credentials, or personal data