CVE-2026-9307
Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.
NVD · uneditedA sensitive information disclosure security issue exists within the affected CompactLogix controllers. The controller's web server exposes CIP Connection IDs on the diagnostics webpage, which are accessible to any unauthenticated user on the network. This information can be leveraged by an attacker to construct malicious packets, leading to Denial-of-Service.
Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.
dbcve analysis · moderate confidenceCompactLogix controllers have a web server that exposes CIP Connection IDs on a diagnostics webpage to unauthenticated network users. This sensitive information disclosure allows attackers to construct malicious packets leveraging the exposed connection identifiers, leading to denial-of-service conditions.
Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.
CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.
From the vector- Attack vector
- Network
- Complexity
- Low
- Privileges
- None
- Authentication
- X
- User interaction
- None
- Scope
- X
CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:L/VI:N/VA:N/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.
dbcve checksWork through these to decide whether this CVE applies to you.
-
Identify CompactLogix controller on the networkUse network scanning tools or review asset inventory to confirm the device is a CompactLogix controller. Check the device's web interface or use tools like nmap to identify the device type via HTTP headers or banner grabbing on port 80/443.Affected if The target device is a CompactLogix controller with a web-based interface.
-
Verify web server is enabledAttempt to access the controller's web interface by navigating to its IP address over HTTP (port 80) or HTTPS (port 443). Use a browser or curl command: curl -k http://<controller-ip>Affected if The web interface responds and is reachable on standard HTTP/HTTPS ports.
-
Check if diagnostics page is accessible without authenticationNavigate to common diagnostic paths such as /diagnostics, /status, or /cippath on the controller's web server. Try accessing the page directly without providing any login credentials.Affected if The diagnostics webpage loads and displays information without requiring user authentication.
-
Verify CIP Connection ID exposureOn the accessible diagnostics page, look for fields or values labeled as CIP Connection ID, Connection ID, CIP Connection, or similar identifiers. Note whether numeric connection identifiers are visible in plain text.Affected if CIP Connection IDs or similar connection identifier values are visible in plain text on an unauthenticated diagnostics page.
If a CompactLogix controller has its web server enabled and exposes a diagnostics page that reveals CIP Connection IDs to unauthenticated users, the environment is affected by this vulnerability.
Generated from the published advisory. Verify against your own configuration.
Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.
From vendor dataRestrict network access to the controller's web server via network segmentation or firewall rules, or disable the web server if not required for operations. Consider applying vendor firmware updates if available.
- Consultation4.0 h
- Implementation8.0 h
- Testing4.0 h
- Review / QA2.0 h
An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $5,120.
Scan for this in your stack
Free · runs locallyCheck whether your project pulls in CVE-2026-9307 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.
References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.
Primary sourcesPractitioner notes
ContributedPeer-ranked notes from engineers who’ve handled CVE-2026-9307 in production — separate from our analysis above.
The advisory tells you what broke. It rarely tells you what actually worked. If you’ve dealt with this one, that detail is what the next engineer is searching for.
- The version that genuinely resolved it — not the one the vendor claimed
- A config change or rule that shut the vector down
- A gotcha in the upgrade path that cost you an afternoon
No notes yet
Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.
A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.
- Verified mitigations, workarounds, and config changes
- Version or environment caveats, and links to real fixes
- No weaponised exploit code, or anything meant to cause harm
- No spam, self-promotion, credentials, or personal data