Simatic S7 1200 FirmwareOperating system · Siemens

CVE-2013-0700

HIGH · 7.8 CVSS v2.0 Published 2013-04-22
Fix available
A fix is available. Upgrade to 4.0 or later.
See remediation →
87/100
Remediation priority · High
Remotely reachable No privileges Zero-click

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
Siemens SIMATIC S7-1200 PLCs 2.x and 3.x allow remote attackers to cause a denial of service (defect-mode transition and control outage) via crafted packets to TCP port 102 (aka the ISO-TSAP port).

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · high confidence

Siemens SIMATIC S7-1200 PLCs versions 2.x and 3.x contain a vulnerability where remote attackers can send crafted packets to TCP port 102 (ISO-TSAP), the protocol used for S7 communication. This causes the PLC to transition to defect mode, resulting in a denial of service and loss of control operations.

MitigationRestrict network access to TCP port 102 on affected PLCs using network segmentation and firewalls; apply Siemens firmware updates to resolve the vulnerability.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

Affected products & versions What the vendor confirmedThe version ranges the vendor confirmed as vulnerable. If your version sits inside a range here, treat yourself as exposed until you have upgraded.

NVD · CPE data
Simatic S7 1200 FirmwareOperating system
Affected:< 4.0
Simatic S7 1200 Cpu 1211c FirmwareOperating system
Affected:< 4.0
Simatic S7 1200 Cpu 1212c FirmwareOperating system
Affected:< 4.0
Simatic S7 1200 Cpu 1212fc FirmwareOperating system
Affected:< 4.0
Simatic S7 1200 Cpu 1214 Fc FirmwareOperating system
Affected:< 4.0
Simatic S7 1200 Cpu 1214c FirmwareOperating system
Affected:< 4.0
Simatic S7 1200 Cpu 1215 Fc FirmwareOperating system
Affected:< 4.0
Simatic S7 1200 Cpu 1215c FirmwareOperating system
Affected:< 4.0

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
Low
Authentication
None
Confidentiality
None
Integrity
None
Availability
Complete

AV:N/AC:L/Au:N/C:N/I:N/A:C

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Identify the S7-1200 CPU model
    Check the device labeling on the PLC physical housing, or access the device via TIA Portal project properties, or view the device overview in the web-based management interface. Look for model numbers such as 1211c, 1212c, 1212fc, 1214Fc, 1214c, 1215Fc, or 1215c.
    Affected if The device is a Siemens Simatic S7-1200 CPU of the models listed in the affected products
  2. Check the PLC firmware version
    Access the PLC through TIA Portal and view the device properties to read the firmware version, or use the web-based management portal of the PLC, or check the version displayed on the PLC's physical display under device information. Record the firmware version number.
    Affected if The firmware version is 2.x or 3.x, meaning any version less than 4.0
  3. Verify TCP port 102 accessibility
    Use a network scanning tool such as nmap or PowerShell Test-NetConnection to probe TCP port 102 (ISO-TSAP) on the PLC IP address. This is the default port for S7 communication.
    Affected if TCP port 102 is reachable from network segments that are not trusted or are exposed to external systems
  4. Check PLC operational status
    Access the PLC diagnostics in TIA Portal, check the web-based management status page, or observe the physical LED indicators on the PLC. Specifically look for indicators of defect mode or communication failures.
    Affected if The PLC is in defect mode, showing STOP with a red SF or BF LED, or experiencing communication failures on port 102

A user is affected if they have a Siemens Simatic S7-1200 CPU (1211c, 1212c, 1212fc, 1214Fc, 1214c, 1215Fc, or 1215c) running firmware version less than 4.0, with TCP port 102 accessible from an untrusted network segment.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

From vendor data
Upgrade available Upgrade to 4.0 or later
Fixed in 4.0
Interim mitigation

Restrict network access to TCP port 102 on affected PLCs using network segmentation and firewalls; apply Siemens firmware updates to resolve the vulnerability.

Fix this in Simatic S7 1200 Firmware Scoped from the published advisory
  • Consultation8.0 h
  • Implementation12.0 h
  • Testing8.0 h
  • Review / QA4.0 h
32.0 hours of engineering $5,680
Get the upgrade done

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $9,088.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2013-0700 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2013-0700 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data