CVE-2015-8214
Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.
NVD · uneditedA vulnerability has been identified in SIMATIC NET CP 342-5 (incl. SIPLUS variants) (All versions), SIMATIC NET CP 343-1 Advanced (incl. SIPLUS variants) (All versions < V3.0.44), SIMATIC NET CP 343-1 Lean (incl. SIPLUS variants) (All versions < V3.1.1), SIMATIC NET CP 343-1 Standard (incl. SIPLUS variants) (All versions < V3.1.1), SIMATIC NET CP 443-1 Advanced (incl. SIPLUS variants) (All versions < V3.2.9), SIMATIC NET CP 443-1 Standard (incl. SIPLUS variants) (All versions < V3.2.9), SIMATIC NET CP 443-5 Basic (incl. SIPLUS variants) (All versions), SIMATIC NET CP 443-5 Extended (All versions), TIM 3V-IE / TIM 3V-IE Advanced (incl. SIPLUS NET variants) (All versions < V2.6.0), TIM 3V-IE DNP3 (incl. SIPLUS NET variants) (All versions < V3.1.0), TIM 4R-IE (incl. SIPLUS NET variants) (All versions < V2.6.0), TIM 4R-IE DNP3 (incl. SIPLUS NET variants) (All versions < V3.1.0). The implemented access protection level enforcement of the affected communication processors (CP) could possibly allow unauthenticated users to perform administrative operations on the CPs if network access (port 102/TCP) is available and the CPs' configuration was stored on their corresponding CPUs.
Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.
dbcve analysis · high confidenceThis is an authentication bypass vulnerability in Siemens SIMATIC NET communication processors (CP 342-5, CP 343-1 variants, CP 443-1 variants, CP 443-5, and TIM devices). The access protection level enforcement fails to properly authenticate users, allowing unauthenticated attackers to perform administrative operations via port 102/TCP when the CP configuration is stored on the corresponding CPU.
Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.
Affected products & versions What the vendor confirmedThe version ranges the vendor confirmed as vulnerable. If your version sits inside a range here, treat yourself as exposed until you have upgraded.
NVD · CPE dataall versionsall versionsall versions<= 3.0all versionsCVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.
From the vector- Attack vector
- Network
- Complexity
- Low
- Authentication
- None
- Confidentiality
- Partial
- Integrity
- Complete
- Availability
- Complete
AV:N/AC:L/Au:N/C:P/I:C/A:C
Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.
dbcve checksWork through these to decide whether this CVE applies to you.
-
Identify the SIMATIC device modelAccess the device via SIMATIC Manager or industrial management software and retrieve the exact model number (CP 342-5, CP 343-1, CP 443-1, CP 443-5, TIM 3v IE, or TIM 4r IE)Affected if The model is one of: CP 343-1, CP 443-1, TIM 3v IE, or TIM 4r IE (CP 342-5 and CP 443-5 are also listed in the summary but have no version range specified)
-
Determine the firmware versionUse SIMATIC Manager, STEP 7, or the device web interface to query the firmware version installed on the communication processorAffected if The firmware version is all versions for CP 443-1 and TIM variants, or version 3.0 or lower for CP 343-1
-
Verify port 102/TCP accessibilityPerform a network port scan targeting the device on TCP port 102 (using nmap -p 102 <device_ip> or similar) to determine if the port is exposed to network segments accessible to attackersAffected if Port 102/TCP is open and accessible from untrusted network segments
-
Check if CP configuration is stored on the CPUReview the PLC/CPU configuration in STEP 7 or SIMATIC Manager to determine whether the CP (Communication Processor) configuration is stored on the CPU rather than on the CP itselfAffected if The CP configuration is stored on the CPU (this is the specific condition that enables the vulnerability)
-
Assess network isolationReview firewall rules, VLAN configurations, and network segmentation to determine if the device and port 102 are protected from untrusted network accessAffected if No firewall or VLAN isolation exists between the device and untrusted networks, or port 102 is directly accessible from outside
The environment is affected if a CP 343-1 (firmware <=3.0), CP 443-1, TIM 3v IE, or TIM 4r IE device has port 102/TCP exposed and stores its CP configuration on the CPU, allowing unauthenticated administrative access.
Generated from the published advisory. Verify against your own configuration.
Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.
dbcve · scopedApply vendor-supplied firmware updates to all affected CP devices (specific version thresholds vary by model: CP 343-1 needs V3.0.44/V3.1.1, CP 443-1 needs V3.2.9, TIM variants need V2.6.0/V3.1.0). Where patches are unavailable, restrict network access to port 102/TCP via firewalls/VLANs and avoid storing CP configurations on CPUs.
CP 343-1 Advanced: V3.0.44+; CP 343-1 Lean/Standard: V3.1.1+; CP 443-1 Advanced/Standard: V3.2.9+; TIM 3V-IE/TIM 4R-IE: V2.6.0+; TIM 3V-IE DNP3/TIM 4R-IE DNP3: V3.1.0+
- 1. Identify the specific CP model (e.g., CP 343-1, CP 443-1, TIM 3V-IE, TIM 4R-IE) from your Siemens equipment.
- 2. Access the Siemens Industry Online Support portal at support.industry.siemens.com or cert-portal.siemens.com to locate the appropriate firmware update.
- 3. Download the fixed firmware version for your specific CP model: CP 343-1 Advanced upgrade to V3.0.44 or later; CP 343-1 Lean/Standard upgrade to V3.1.1 or later; CP 443-1 Advanced/Standard upgrade to V3.2.9 or later; TIM 3V-IE/TIM 4R-IE upgrade to V2.6.0 or later; TIM 3V-IE DNP3/TIM 4R-IE DNP3 upgrade to V3.1.0 or later.
- 4. Review the firmware update documentation for any prerequisites or installation procedures.
- 5. Back up the current CP configuration before applying the update.
- 6. Apply the firmware update via Siemens STEP 7/TIA Portal or the CP's web-based configuration interface.
- 7. After updating, verify that the access protection is properly configured and that port 102 access is restricted to authorized hosts only.
- 8. Consider network segmentation to isolate industrial control system devices from untrusted networks as an additional mitigation.
Generated from the published advisory — verify against the referenced sources before acting.
- Consultation6.0 h
- Implementation12.0 h
- Testing8.0 h
- Review / QA4.0 h
An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $8,448.
Scan for this in your stack
Free · runs locallyCheck whether your project pulls in CVE-2015-8214 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.
References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.
Primary sourcesPractitioner notes
ContributedPeer-ranked notes from engineers who’ve handled CVE-2015-8214 in production — separate from our analysis above.
The advisory tells you what broke. It rarely tells you what actually worked. If you’ve dealt with this one, that detail is what the next engineer is searching for.
- The version that genuinely resolved it — not the one the vendor claimed
- A config change or rule that shut the vector down
- A gotcha in the upgrade path that cost you an afternoon
No notes yet
Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.
A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.
- Verified mitigations, workarounds, and config changes
- Version or environment caveats, and links to real fixes
- No weaponised exploit code, or anything meant to cause harm