1766 L32bxba FirmwareOperating system · Rockwellautomation

CVE-2017-16740

CRITICAL · 10.0 CVSS v3.0 Published 2018-01-09
Fix available
A fix is available. Upgrade to after 21.002 or later.
See remediation →
100/100
Remediation priority · Urgent
Remotely reachable No privileges Zero-click

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
A Buffer Overflow issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1400 Controllers, Series B and C Versions 21.002 and earlier. The stack-based buffer overflow vulnerability has been identified, which may allow remote code execution.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · high confidence

A stack-based buffer overflow vulnerability exists in Rockwell Automation Allen-Bradley MicroLogix 1400 Controllers (Series B and C, version 21.002 and earlier). The overflow can be triggered remotely, potentially allowing an attacker to execute arbitrary code on the controller.

MitigationUpdate MicroLogix 1400 firmware to a version beyond 21.002 when available, and restrict network access to the controllers using network segmentation and firewalls to reduce attack surface.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

Affected products & versions What the vendor confirmedThe version ranges the vendor confirmed as vulnerable. If your version sits inside a range here, treat yourself as exposed until you have upgraded.

NVD · CPE data
1766 L32bxba FirmwareOperating system
Affected:<= 21.002
1766 L32awa FirmwareOperating system
Affected:<= 21.002
1766 L32bxb FirmwareOperating system
Affected:<= 21.002
1766 L32bwaa FirmwareOperating system
Affected:<= 21.002
1766 L32awaa FirmwareOperating system
Affected:<= 21.002
1766 L32bwa FirmwareOperating system
Affected:<= 21.002

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
Low
Privileges
None
User interaction
None
Scope
Changed
Confidentiality
High
Integrity
High
Availability
High

CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Identify the controller model number
    Locate the physical controller label on the device, or use RSLinx Classic software to browse the network and identify the connected MicroLogix 1400 controller. The model number should be one of: 1766-L32BXBA, 1766-L32AWA, 1766-L32BXB, 1766-L32BWAA, 1766-L32AWAA, or 1766-L32BWA.
    Affected if The model number matches one of the six affected variants listed.
  2. Determine the controller series
    Check whether the controller is Series B or Series C. This information is typically visible on the physical device label, in RSLinx under the controller properties, or via the web interface if enabled.
    Affected if The controller is identified as Series B or Series C.
  3. Check the installed firmware version
    Retrieve the firmware version from the controller. This can be done through: (1) the LCD display on the controller (navigate to the controller status screen), (2) RSLinx Classic - right-click the controller and view device properties, (3) the built-in web server if it has been enabled, or (4) BOOTP server logs showing the controller's bootp response.
    Affected if The firmware version is 21.002 or lower.
  4. Verify network accessibility
    Determine if the controller is accessible over the network via Ethernet/IP. Attempt to ping the controller IP address and verify that EtherNet/IP communication is possible from your workstation using RSLinx or a similar tool.
    Affected if The controller is network-accessible and the firmware version is 21.002 or earlier.

You are affected if you have a MicroLogix 1400 controller matching one of the listed model numbers, running Series B or C firmware version 21.002 or earlier, and the device is accessible on your network.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

dbcve · scoped
Upgrade available Upgrade to a release after 21.002
Interim mitigation

Update MicroLogix 1400 firmware to a version beyond 21.002 when available, and restrict network access to the controllers using network segmentation and firewalls to reduce attack surface.

Recommended fix Moderate confidence

Firmware version later than 21.002 (contact Rockwell Automation for the specific patched release)

  1. Identify the exact controller model (1766 L32bxba, L32awa, L32bxb, L32bwaa, L32awaa, or L32bwa) from the MicroLogix 1400 Series B or C line
  2. Contact Rockwell Automation technical support or visit the official support portal to obtain the security firmware update that addresses CVE-2017-16740
  3. Backup the current controller configuration before performing any firmware update
  4. Follow Rockwell Automation's official firmware update procedure for MicroLogix 1400 controllers using their recommended programming software (e.g., RSLogix 500, FactoryTalk Asset Manager)
  5. Verify the firmware version after update matches the patched release version
  6. Test the controller functionality and validate that the buffer overflow vulnerability is no longer exploitable
Caveat Industrial control system firmware upgrades carry operational risk - test in a non-production environment first and plan for potential downtime

Generated from the published advisory — verify against the referenced sources before acting.

Fix this in 1766 L32bxba Firmware Scoped from the published advisory
  • Consultation8.0 h
  • Implementation4.0 h
  • Testing6.0 h
  • Review / QA4.0 h
22.0 hours of engineering $3,940
Get the upgrade done

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $6,304.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2017-16740 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2017-16740 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data