Apogee Mbc \(ppc\) \(p2 Ethernet\) FirmwareOperating system · Siemens

CVE-2021-27391

CRITICAL · 9.8 CVSS v3.1 Published 2021-09-14
Fix available
A fix is available. Upgrade to 3.5.3 or later.
See remediation →
100/100
Remediation priority · Urgent
Remotely reachable No privileges Zero-click Patch available

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
A vulnerability has been identified in APOGEE MBC (PPC) (P2 Ethernet) (All versions >= V2.6.3), APOGEE MEC (PPC) (P2 Ethernet) (All versions >= V2.6.3), APOGEE PXC Compact (BACnet) (All versions < V3.5.3), APOGEE PXC Compact (P2 Ethernet) (All versions >= V2.8), APOGEE PXC Modular (BACnet) (All versions < V3.5.3), APOGEE PXC Modular (P2 Ethernet) (All versions >= V2.8), TALON TC Compact (BACnet) (All versions < V3.5.3), TALON TC Modular (BACnet) (All versions < V3.5.3). The web server of affected devices lacks proper bounds checking when parsing the Host parameter in HTTP requests, which could lead to a buffer overflow. An unauthenticated remote attacker could exploit this vulnerability to execute arbitrary code on the device with root privileges.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis
How this class of weakness works · CWE-120

A fixed-size buffer is filled without checking the length of the incoming data, so it overflows into neighbouring memory. This is the classic overflow attackers use to overwrite return addresses and hijack execution. The fix is strict length checks and safe, bounded string and memory functions.

General guidance for the classic buffer overflow class — the official description and references above are authoritative for this specific CVE. Want a bespoke review and a reviewed fix? Ask our team →

Affected products & versions What the vendor confirmedThe version ranges the vendor confirmed as vulnerable. If your version sits inside a range here, treat yourself as exposed until you have upgraded.

NVD · CPE data
Apogee Mbc \(ppc\) \(p2 Ethernet\) FirmwareOperating system
Affected:<= 2.6.3
Apogee Mec \(ppc\) \(p2 Ethernet\) FirmwareOperating system
Affected:<= 2.6.3
Apogee Pxc Bacnet Automation Controller FirmwareOperating system
Affected:< 3.5.3
Apogee Pxc Compact \(p2 Ethernet\) FirmwareOperating system
Affected:<= 2.8
Apogee Pxc Modular \(bacnet\) FirmwareOperating system
Affected:< 3.5.3
Apogee Pxc Modular \(p2 Ethernet\) FirmwareOperating system
Affected:<= 2.8
Talon Tc Compact \(bacnet\) FirmwareOperating system
Affected:< 3.5.3
Talon Tc Modular \(bacnet\) FirmwareOperating system
Affected:< 3.5.3

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
Low
Privileges
None
User interaction
None
Scope
Unchanged
Confidentiality
High
Integrity
High
Availability
High

CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

dbcve · scoped
Upgrade available Upgrade to 3.5.3 or later
Fixed in 3.5.3
Recommended fix High confidence

Firmware version 3.5.3 or later for BACnet variants; firmware version >2.6.3 (e.g., 2.6.4+) for MBC/MEC P2 Ethernet; firmware version >2.8 (e.g., 2.8.1+) for PXC P2 Ethernet variants

  1. 1. Identify the exact model and current firmware version of the affected Apogee or Talon device using the device's web interface or management console.
  2. 2. Navigate to the Siemens Product CERT portal and download the patch document from https://cert-portal.siemens.com/productcert/pdf/ssa-944498.pdf to obtain the official fixed firmware versions and upgrade instructions.
  3. 3. For Apogee MBC (PPC) and MEC (PPC) P2 Ethernet devices: Upgrade firmware to a version greater than 2.6.3 (e.g., 2.6.4 or later as specified in the Siemens patch).
  4. 4. For Apogee PXC Compact (BACnet) and PXC Modular (BACnet) devices: Upgrade firmware to version 3.5.3 or later.
  5. 5. For Apogee PXC Compact (P2 Ethernet) and PXC Modular (P2 Ethernet) devices: Upgrade firmware to a version greater than 2.8 (e.g., 2.8.1 or later as specified in the Siemens patch).
  6. 6. For Talon TC Compact (BACnet) and Talon TC Modular (BACnet) devices: Upgrade firmware to version 3.5.3 or later.
  7. 7. Before upgrading, backup the device configuration according to the procedures outlined in the device manual.
  8. 8. Apply the firmware upgrade using the manufacturer's recommended upgrade procedure (typically via the device's web interface or a dedicated upgrade tool).
Caveat Review Siemens patch documentation for any configuration changes or compatibility considerations before upgrading

Generated from the published advisory — verify against the referenced sources before acting.

We can perform the upgrade in your staging environment and verify nothing breaks — typical engagement from $3,550. Get the upgrade done

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2021-27391 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2021-27391 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data