Modular Switchgear Monitoring FirmwareOperating system · Hitachienergy

CVE-2021-40335

HIGH · 8.8 CVSS v3.1 Published 2022-07-25
Fix available
A fix is available. Upgrade to after 2.2.0 or later.
See remediation →
95/100
Remediation priority · Urgent
Remotely reachable No privileges

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
A vulnerability exists in the HTTP web interface where the web interface does not sufficiently verify if a well-formed, valid, consistent request was intentionally provided by the user who submitted the request. This cause a Cross Site Request Forgery (CSRF), which if exploited could lead an attacker to gain unauthorized access to the web application and perform an unwanted operation on it without the knowledge of the legitimate user. An attacker, who successfully makes an MSM user who has already established a session to MSM web interface clicks a forged link to the MSM web interface, e.g., link is sent per E-Mail, could perform harmful command on MSM through its web server interface. This issue affects: Hitachi Energy MSM V2.2 and prior versions.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · high confidence

Hitachi Energy MSM V2.2 and prior versions contain a Cross-Site Request Forgery (CSRF) vulnerability in the HTTP web interface. The application lacks proper verification (anti-CSRF tokens or request validation) to confirm that requests originate from the legitimate authenticated user, allowing attackers to trick authenticated users into performing unintended operations via malicious links.

MitigationImplement anti-CSRF tokens or unique request identifiers for all state-changing operations (forms, API endpoints), enable SameSite cookie attributes, and add referrer/Origin header validation. User sessions should also include secondary confirmation for sensitive operations.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

Affected products & versions What the vendor confirmedThe version ranges the vendor confirmed as vulnerable. If your version sits inside a range here, treat yourself as exposed until you have upgraded.

NVD · CPE data
Modular Switchgear Monitoring FirmwareOperating system
Affected:<= 2.2.0

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
Low
Privileges
None
User interaction
Required
Scope
Unchanged
Confidentiality
High
Integrity
High
Availability
High

CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Confirm MSM web interface is accessible
    Access the device's IP address via HTTP/HTTPS in a browser to verify the Hitachi Energy Modular Switchgear Monitoring web interface is reachable
    Affected if The MSM web interface is exposed and accessible on the network
  2. Identify firmware version
    Log into the MSM web interface and navigate to System Information, About, or Settings page to view the firmware version. Alternatively, check the HTTP response headers or error pages for version information
    Affected if The installed firmware version is 2.2.0 or lower
  3. Inspect HTML forms for anti-CSRF tokens
    View the page source (right-click > View Page Source) of state-changing forms (configuration, control actions, user management) and search for hidden input fields containing names like 'csrf', 'token', 'nonce', or 'xsrf'. Check if each form submission includes a unique token parameter
    Affected if Forms lack hidden anti-CSRF token fields or the tokens are missing from form submissions
  4. Verify cookie SameSite attributes
    Open browser developer tools (F12), go to Application/Storage tab, examine cookies set by the MSM application, and inspect the SameSite and Secure attributes for session cookies
    Affected if Session cookies lack SameSite=Strict or SameSite=Lax attributes
  5. Test referrer/Origin header validation
    Submit a form request with a mismatched or missing Referer/Origin header (using a tool like Burp Suite or curl) to determine if the application rejects the request
    Affected if The application accepts requests without validating Referer or Origin headers

The environment is affected if the MSM firmware version is 2.2.0 or lower AND the web interface lacks anti-CSRF tokens in forms, proper cookie attributes, and referrer/Origin validation.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

From vendor data
Upgrade available Upgrade to a release after 2.2.0
Interim mitigation

Implement anti-CSRF tokens or unique request identifiers for all state-changing operations (forms, API endpoints), enable SameSite cookie attributes, and add referrer/Origin header validation. User sessions should also include secondary confirmation for sensitive operations.

Fix this in Modular Switchgear Monitoring Firmware Scoped from the published advisory
  • Consultation4.0 h
  • Implementation12.0 h
  • Testing6.0 h
  • Review / QA4.0 h
26.0 hours of engineering $4,580
Get the upgrade done

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $7,328.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2021-40335 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2021-40335 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data