Modular Switchgear Monitoring FirmwareOperating system · Hitachienergy

CVE-2021-40336

HIGH · 8.8 CVSS v3.1 Published 2022-07-25
Fix available
A fix is available. Upgrade to after 2.2.0 or later.
See remediation →
95/100
Remediation priority · Urgent
Remotely reachable No privileges

Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.

NVD · unedited
A vulnerability exists in the http web interface where the web interface does not validate data in an HTTP header. This causes a possible HTTP response splitting, which if exploited could lead an attacker to channel down harmful code into the user’s web browser, such as to steal the session cookies. Thus, an attacker who successfully makes an MSM user who has already established a session to MSM web interface clicks a forged link to the MSM web interface, e.g., the link is sent per E-Mail, could trick the user into downloading malicious software onto his computer. This issue affects: Hitachi Energy MSM V2.2 and prior versions.

Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.

dbcve analysis · high confidence

Hitachi Energy MSM V2.2 and prior versions contain an HTTP response splitting (CRLF injection) vulnerability in the web interface. The application fails to validate data in HTTP headers, allowing attackers to inject malicious headers via specially crafted links. When a user with an active session clicks a forged link, attackers can steal session cookies or trick users into downloading malicious software.

MitigationImplement proper validation and sanitization of all HTTP header data to prevent CRLF injection. Header values should be checked for carriage return (\r) and line feed (\n) characters and rejected or sanitized before being used in HTTP responses.

Verify against the referenced sources before acting — the references below are authoritative for this CVE, this summary is not.

Affected products & versions What the vendor confirmedThe version ranges the vendor confirmed as vulnerable. If your version sits inside a range here, treat yourself as exposed until you have upgraded.

NVD · CPE data
Modular Switchgear Monitoring FirmwareOperating system
Affected:<= 2.2.0

CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.

From the vector
Attack vector
Network
Complexity
Low
Privileges
None
User interaction
Required
Scope
Unchanged
Confidentiality
High
Integrity
High
Availability
High

CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H

Am I affected? How to checkSteps we derive from the advisory and the affected-version data, so you can decide whether this CVE reaches your setup. They are a guide, not a scan — your own configuration is the authority.

dbcve checks

Work through these to decide whether this CVE applies to you.

  1. Confirm Hitachi Energy MSM is deployed
    Identify if the Hitachi Energy Modular Switchgear Monitoring product is installed in your environment. Check network scans, asset inventories, or consult with IT infrastructure teams for systems running this software.
    Affected if The system has Hitachi Energy MSM installed
  2. Check installed firmware version
    Access the MSM device console or admin interface and locate the firmware version information. Compare this version number against the affected range of <= 2.2.0.
    Affected if The installed firmware version is 2.2.0 or prior
  3. Verify web interface is enabled
    Determine if the MSM web interface is accessible and active. Check network configurations, firewall rules, or the device administration panel to confirm the HTTP web service is running.
    Affected if The web interface is enabled and accessible over HTTP/HTTPS
  4. Inspect HTTP header handling
    If you have authorized access, test the web interface by submitting requests with special characters in input fields that might be reflected in HTTP headers. Monitor responses for any indication that carriage return (\r) and line feed (\n) characters are not being filtered or rejected.
    Affected if The application does not sanitize or reject CRLF characters in header inputs

You are affected if your installed Hitachi Energy MSM firmware version is 2.2.0 or prior AND the web interface is enabled and accessible, as the CRLF injection vulnerability exists in the unpatched web interface.

Generated from the published advisory. Verify against your own configuration.

Check your environment

Paste your version and any relevant configuration and it will be compared against the affected criteria above. Do not include secrets or credentials.

AI-assisted, checked against the advisory. Informational, not a guarantee.

Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.

From vendor data
Upgrade available Upgrade to a release after 2.2.0
Interim mitigation

Implement proper validation and sanitization of all HTTP header data to prevent CRLF injection. Header values should be checked for carriage return (\r) and line feed (\n) characters and rejected or sanitized before being used in HTTP responses.

Fix this in Modular Switchgear Monitoring Firmware Scoped from the published advisory
  • Consultation3.0 h
  • Implementation6.0 h
  • Testing3.0 h
  • Review / QA2.0 h
14.0 hours of engineering $2,490
Get the upgrade done

An estimate, not a bill — we confirm scope with you before any work starts. Need it this week? Rush from $3,984.

Scan for this in your stack

Free · runs locally
dbcve dependency scanner

Check whether your project pulls in CVE-2021-40336 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.

References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.

Primary sources

Practitioner notes

Contributed

Peer-ranked notes from engineers who’ve handled CVE-2021-40336 in production — separate from our analysis above.

No notes yet

Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.

What this is

A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.

What belongs here
  • Verified mitigations, workarounds, and config changes
  • Version or environment caveats, and links to real fixes
  • No weaponised exploit code, or anything meant to cause harm
  • No spam, self-promotion, credentials, or personal data