CVE-2024-22039
Official description Straight from the sourceThe vendor's or NVD's own wording, published unedited. Authoritative, but often terse — it says what broke, rarely what to do.
NVD · uneditedA vulnerability has been identified in Cerberus PRO EN Engineering Tool (All versions < IP8), Cerberus PRO EN Fire Panel FC72x IP6 (All versions < IP6 SR3), Cerberus PRO EN Fire Panel FC72x IP7 (All versions < IP7 SR5), Cerberus PRO EN X200 Cloud Distribution IP7 (All versions < V3.0.6602), Cerberus PRO EN X200 Cloud Distribution IP8 (All versions < V4.0.5016), Cerberus PRO EN X300 Cloud Distribution IP7 (All versions < V3.2.6601), Cerberus PRO EN X300 Cloud Distribution IP8 (All versions < V4.2.5015), Cerberus PRO UL Compact Panel FC922/924 (All versions < MP4), Cerberus PRO UL Engineering Tool (All versions < MP4), Cerberus PRO UL X300 Cloud Distribution (All versions < V4.3.0001), Desigo Fire Safety UL Compact Panel FC2025/2050 (All versions < MP4), Desigo Fire Safety UL Engineering Tool (All versions < MP4), Desigo Fire Safety UL X300 Cloud Distribution (All versions < V4.3.0001), Sinteso FS20 EN Engineering Tool (All versions < MP8), Sinteso FS20 EN Fire Panel FC20 MP6 (All versions < MP6 SR3), Sinteso FS20 EN Fire Panel FC20 MP7 (All versions < MP7 SR5), Sinteso FS20 EN X200 Cloud Distribution MP7 (All versions < V3.0.6602), Sinteso FS20 EN X200 Cloud Distribution MP8 (All versions < V4.0.5016), Sinteso FS20 EN X300 Cloud Distribution MP7 (All versions < V3.2.6601), Sinteso FS20 EN X300 Cloud Distribution MP8 (All versions < V4.2.5015), Sinteso Mobile (All versions < V3.0.0). The network communication library in affected systems does not validate the length of certain X.509 certificate attributes which might result in a stack-based buffer overflow. This could allow an unauthenticated remote attacker to execute code on the underlying operating system with root privileges.
Technical summary Written by usOur analysis, written from the advisory, the CVSS vector and the affected-version data. It adds context the advisory leaves out, and never invents facts that are not in the source.
dbcve analysisA fixed-size buffer is filled without checking the length of the incoming data, so it overflows into neighbouring memory. This is the classic overflow attackers use to overwrite return addresses and hijack execution. The fix is strict length checks and safe, bounded string and memory functions.
General guidance for the classic buffer overflow class — the official description and references above are authoritative for this specific CVE. Want a bespoke review and a reviewed fix? Ask our team →
Affected products & versions What the vendor confirmedThe version ranges the vendor confirmed as vulnerable. If your version sits inside a range here, treat yourself as exposed until you have upgraded.
NVD · CPE data< ip8< ip8< 4.0.5016< 4.2.5015< mp8< mp8< 4.0.5016< 4.2.5015CVSS breakdown How the score is builtThe industry scoring standard. It rates how the flaw is reached, what it takes to exploit, and what an attacker gains — the score is derived from those, not the other way round.
From the vector- Attack vector
- Network
- Complexity
- Low
- Privileges
- None
- User interaction
- None
- Scope
- Unchanged
- Confidentiality
- High
- Integrity
- High
- Availability
- High
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Remediation Closing itWhat it takes to close this. Where a vendor fix exists we point at it; where none exists we say so plainly, and can build one. Effort estimates are scoped from the advisory, not from your codebase.
dbcve · scoped4.0.50164.2.5015
Upgrade to IP8 (Cerberus PRO EN) or MP8 (Sinteso FS20 EN) for Engineering Tools; upgrade to respective SR versions or next major version for Fire Panels; upgrade to V4.0.5016 (X200) or V4.2.5015 (X300) for Cloud Distribution
- 1. Identify the specific product and current installed version from the affected product list (Engineering Tool, Fire Panel FC72x, X200 Cloud Distribution, or X300 Cloud Distribution).
- 2. Determine the IP/MP version branch currently in use (IP6, IP7, IP8, MP6, MP7, or MP8).
- 3. Navigate to the Siemens productcert portal at https://cert-portal.siemens.com/productcert/html/ssa-225840.html to obtain the specific patch or upgrade package.
- 4. For Cerberus PRO EN Engineering Tool: upgrade to version IP8 or later.
- 5. For Cerberus PRO EN Fire Panel FC72x: upgrade to IP6 SR3, IP7 SR5, or IP8 (depending on branch).
- 6. For Cerberus PRO EN X200 Cloud Distribution: upgrade to V3.0.6602 (IP7 branch) or V4.0.5016 (IP8 branch).
- 7. For Cerberus PRO EN X300 Cloud Distribution: upgrade to V3.2.6601 (IP7 branch) or V4.2.5015 (IP8 branch).
- 8. For Sinteso FS20 EN Engineering Tool: upgrade to version MP8 or later.
Generated from the published advisory — verify against the referenced sources before acting.
Scan for this in your stack
Free · runs locallyCheck whether your project pulls in CVE-2024-22039 — or any other known-vulnerable package — straight from your lock files. Free and open source; it runs locally and uploads nothing.
References Go to the primary sourcePrimary sources — vendor advisories, patches and trackers. Where our summary and a reference disagree, the reference wins.
Primary sourcesPractitioner notes
ContributedPeer-ranked notes from engineers who’ve handled CVE-2024-22039 in production — separate from our analysis above.
The advisory tells you what broke. It rarely tells you what actually worked. If you’ve dealt with this one, that detail is what the next engineer is searching for.
- The version that genuinely resolved it — not the one the vendor claimed
- A config change or rule that shut the vector down
- A gotcha in the upgrade path that cost you an afternoon
No notes yet
Be the first to add a field note for this CVE — a mitigation you’ve verified, a version caveat, or a link to a working fix. Sign in above to contribute.
A place for practitioners to share what actually worked: a mitigation you’ve tested, a configuration change, a version- or environment-specific caveat, or a link to a verified patch. The most useful notes rise to the top as peers upvote them, so the signal stays high.
- Verified mitigations, workarounds, and config changes
- Version or environment caveats, and links to real fixes
- No weaponised exploit code, or anything meant to cause harm